H
ANDLING
S
ULFUR
H
EXAFLUORIDE
REV7
/REV3
OI 250 (EN)
3
Handling Sulfur Hexafluoride
Sulfur hexafluoride (SF
6
) is an inert gas that is colorless and odor-
less, chemically neutral, non-combustible and approximately five
times heavier than air. It is non-toxic and is not an ozone-depleting
substance.
Pure SF
6
is completely safe for human beings and animals physio-
logically. Because of its weight, however, it can displace the air in
poorly ventilated, lower-lying or underground spaces (e.g. base-
ments, cable ducts and maintenance shafts).
SF
6
is not classified as a hazardous substance in European chemi-
cals legislation.
It has no ecotoxic potential and does not contribute to destruction of
the ozone layer. Because of its high global warming potential
(22,200), it can contribute to the greenhouse effect if it is released
into the atmosphere. Therefore do not dump or otherwise discharge
SF
6
to the atmosphere, and reduce incidental emissions wherever
possible.
If SF
6
is used to fill electrical switchgear, it must comply with stan-
dard IEC 60376.
Standards governing SF
6
handling
- IEC 60480 Guidelines for the checking and treatment of sulfur
hexafluoride taken from electrical equipment and specification for
its re-use.
- IEC 62271-4 Use and handling of sulphur hexafluoride (SF
6
) in
high-voltage switchgear and controlgear.
3.1
Safety Precautions When Handling SF
6
3.1.1
Oxygen Displacement
SF
6
is five times heavier than air and can accumulate in underg-
round rooms or poorly ventilated spaces if it gets into the work env-
ironment in large quantities. In such cases air is displaced, which
consequently reduces the amount of oxygen available. If the oxy-
gen concentration drops below 16% (IEC 62271-4), there is the
danger that personnel working in the surrounding area will suffoca-
te. Poorly ventilated or non-ventilated underground spaces such as
basements, cable ducts, maintenance shafts and drainage systems
are especially vulnerable.
3.1.2
Mechanical Handling
The SF
6
operating pressure in the switchgear unit is higher than the
atmospheric air pressure. To avoid the danger of injury resulting
from mechanical breakage of housing components, personnel must
comply with the safety precautions specified in the appropriate
chapters of this operating manual.
Summary of Contents for GL 311 F3/4031 P/VE
Page 2: ......
Page 10: ...INTRODUCTION 10 146 OI 250 EN REV7 REV6...
Page 12: ...SAFETY 12 146 OI 250 EN REV7 REV3...
Page 48: ...INSTALLATION 48 146 OI 250 EN REV7 REV7...
Page 80: ...INSPECTION AND MAINTENANCE 80 146 OI 250 EN REV7 REV3...
Page 102: ...RECONDITIONING 102 146 OI 250 EN REV7 REV7...
Page 104: ...END OF LIFE MANAGEMENT 104 146 OI 250 EN REV7 REV2a...
Page 114: ...SPECIAL EQUIPMENT OPTIONAL 114 146 OI 250 EN REV7 REV0...
Page 128: ...REPLACEMENT PARTS AND ACCESSORIES 128 146 OI 250 EN REV7 REV6...
Page 130: ...HANDLING USED SULFUR HEXAFLUORIDE 130 146 OI 250 EN REV7 REV2...