COMMREQ #5: Clear Circuit Fault Command
This command is used to clear any faults on a specified circuit of a targeted Genius I/O device.
Command Block for the Clear Circuit Fault Command
Address
Command Length
4
A1
No Wait
0
A2
Status Block memory type
70 (%I), 72 (%Q), 8 (%R), 10 (%AI), 12 (%AQ) or 196 (%W)
A3
Status Block offset
Beginning address for the COMMREQ Status Block.
A4
Idle timeout value
0
A5
Max. communications time
0
A6
Command number
5
A7
PROFINET Device number
1-255: The device number of the targeted GCG Genius Gateway.
A8
Genius Device Number
1-29: the SBA of the targeted Genius Device.
A9
Relative Circuit Number
This is the relative number of the circuit within the Genius device. It is
not its reference number assigned in CPU Memory. The first circuit on the
Genius device is considered to be number 1.
For example, to clear faults on discrete I/O block circuit #5, enter 5 here.
For a 4-Input/2-Output analog block, circuit numbers 1 to 4 are for input
channels, 5 and 6 are for output channels.