Chapter 5. Diagnostics
GFK-2892F
March 2019
47
Figure 28: Genius Discrete Block
Failed Switch
Fault Display (Example)
Table Entry
Explanation
Value
Interpretation
Loc
Location of Fault
0.6.D1.r0.s15.ss1
Rack 0 Slot 6 = location of PNC
D1 = Device Number of GCG
s15 = SBA of faulted Genius device
ss1 (Not used for Genius blocks. VersaMax,
90-70 Scanner rack, and Field Control
devices specify the location of module in
fault.)
Circ No.
Genius Device Circuit #
5
Fifth point on the Genius device is faulted
Variable Name Alternate to Ref Address
Will display if variable name has been
assigned
Ref. Address
PLC Reference Address
%QI 00145
Point 145 in %QI table is referenced
Fault Category
Coded Fault Category
Channel Diagnosis
Appears/Disappears
”
Appears
when fault first detected at PLC.
Disappears
when fault has been resolved.
Fault Type
Coded Fault Type
Manufacturer specific
(273)
See table of Fault Types (page 46).
Failed Switch
in this case
Date/Time
Date/Time
Date/Time fault is registered by PLC.
Figure 29: Genius Analog Block
Over Range
Fault Display (Example)
Clearing the RX3i Fault Tables
Clearing the RX3i CPU’s I/O fault tables has no effect on the GCG001 or on the Genius Devices downstream
from it. This action merely clears the I/O Fault Table temporarily. Use the Genius HHM or COMREQs in the PLC
program to exercise I/O points that had previously exhibited faults, and where the underlying field fault