Chapter 2. Installation
22
PACSystems RX3i Genius Communications Gateway
GFK-2892F
Light-Emitting Diode (LED) Indications
The four LEDs in the module header provide a visual indication of the GCG001 module status.
POWER
—
indicates the presence of power to the module.
Green, ON steady
Power supply is good.
OFF
Power supply is off or not good.
OK
—
indicates GCG001 readiness to perform normal module operations.
Green, ON steady
Module able to perform normal operations.
Green/Amber,
blinking
Module loading main operating system
Amber, ON steady
Module loading boot-loader operating system
OFF
Module has an unrecoverable fault or power is not applied.
FAULT
—
indicates the detection of faults by the module.
OFF
No faults present.
Red, blinking 2Hz
DCP Device Identification Signal received on PROFINET.
Red, ON
A fault or other PROFINET diagnostic data exists on the Gateway
CONNECT
—
indicates status of the connection to a PROFINET controller.
OFF
One or more connections with GE PROFINET Controllers have been
established to this device.
Red, blinking
Device trying to connect to a controller.
Continuous if device has not been assigned a valid station name.
Red, ON
No PROFINET Controller connection
The two LEDs associated with each Ethernet port (used here as PROFINET ports) are labelled ACT and LINK.
These LEDs provide information about activity on that particular port.
PORT 1, PORT 2 LINK
—
indicates connection status on Ethernet ports.
Green, ON steady
Ethernet connection established
OFF
No Ethernet connection
PORT 1, PORT 2 ACT
—
indicates activity on PROFINET ports.
Amber, blinking
Communications occurring on port
OFF
No communication
The LED located directly above the Genius connector provides information about the Genius bus.
COM
—
indicates the status of Genius Bus communications.
Green, ON steady
The Genius Bus is configured and operating properly.
Green, blinking
A Genius Bus error has been detected.
OFF
The Genius Bus has failed or no Genius Bus configuration has been
received.