GE Multilin
G60 Generator Protection System
B-43
APPENDIX B
B.4 MEMORY MAPPING
B
A28E
Reserved (10 items)
---
---
1
F001
0
A298
...Repeated for Selector 2
DNP/IEC Points (Read/Write Setting)
A300
DNP/IEC 60870-5-104 Binary Input Points (256 items)
0 to 65535
---
1
F300
0
A400
DNP/IEC 60870-5-104 Analog Input Points (256 items)
0 to 65535
---
1
F300
0
Volts Per Hertz (Read/Write Grouped Setting) (2 modules)
A580
Volts Per Hertz 1 Function
0 to 1
---
1
F102
0 (Disabled)
A581
Volts Per Hertz 1 Source
0 to 5
---
1
F167
0 (SRC 1)
A582
Volts Per Hertz 1 Pickup
0.8 to 4
pu
0.01
F001
80
A583
Volts Per Hertz 1 Curves
0 to 7
---
1
F240
0 (Definite Time)
A584
Volts Per Hertz 1 TD Multiplier
0.05 to 600
---
0.01
F001
100
A585
Volts Per Hertz 1 Block
0 to 65535
---
1
F300
0
A586
Volts Per Hertz 1 Events
0 to 1
---
1
F102
0 (Disabled)
A587
Volts Per Hertz 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A588
Volts Per Hertz 1 T Reset
0 to 1000
s
0.1
F001
10
A589
...Repeated for Volts Per Hertz 2
Volts Per Hertz Actuals (Read Only) (2 modules)
A5A0
Volts Per Hertz 1
0 to 65.535
pu
0.001
F001
0
A5A1
Volts Per Hertz 2
0 to 65.535
pu
0.001
F001
0
Flexcurves C and D (Read/Write Setting)
A600
FlexCurve C (120 items)
0 to 65535
ms
1
F011
0
A680
FlexCurve D (120 items)
0 to 65535
ms
1
F011
0
Non Volatile Latches (Read/Write Setting) (16 modules)
A700
Non-Volatile Latch 1 Function
0 to 1
---
1
F102
0 (Disabled)
A701
Non-Volatile Latch 1 Type
0 to 1
---
1
F519
0 (Reset Dominant)
A702
Non-Volatile Latch 1 Set
0 to 65535
---
1
F300
0
A703
Non-Volatile Latch 1 Reset
0 to 65535
---
1
F300
0
A704
Non-Volatile Latch 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A705
Non-Volatile Latch 1 Events
0 to 1
---
1
F102
0 (Disabled)
A706
Reserved (4 items)
---
---
---
F001
0
A70A
...Repeated for Non-Volatile Latch 2
A714
...Repeated for Non-Volatile Latch 3
A71E
...Repeated for Non-Volatile Latch 4
A728
...Repeated for Non-Volatile Latch 5
A732
...Repeated for Non-Volatile Latch 6
A73C
...Repeated for Non-Volatile Latch 7
A746
...Repeated for Non-Volatile Latch 8
A750
...Repeated for Non-Volatile Latch 9
A75A
...Repeated for Non-Volatile Latch 10
A764
...Repeated for Non-Volatile Latch 11
A76E
...Repeated for Non-Volatile Latch 12
A778
...Repeated for Non-Volatile Latch 13
A782
...Repeated for Non-Volatile Latch 14
A78C
...Repeated for Non-Volatile Latch 15
A796
...Repeated for Non-Volatile Latch 16
Digital Counter (Read/Write Setting) (8 modules)
A800
Digital Counter 1 Function
0 to 1
---
1
F102
0 (Disabled)
A801
Digital Counter 1 Name
---
---
---
F205
“Counter 1"
A807
Digital Counter 1 Units
---
---
---
F206
(none)
A80A
Digital Counter 1 Block
0 to 65535
---
1
F300
0
A80B
Digital Counter 1 Up
0 to 65535
---
1
F300
0
A80C
Digital Counter 1 Down
0 to 65535
---
1
F300
0
A80D
Digital Counter 1 Preset
–2147483647 to
2147483647
---
1
F004
0
Table B–9: MODBUS MEMORY MAP (Sheet 36 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...