GE Multilin
G60 Generator Protection System
B-35
APPENDIX B
B.4 MEMORY MAPPING
B
756A
...Repeated for disconnect switch 3
757F
...Repeated for disconnect switch 4
7594
...Repeated for disconnect switch 5
75A9
...Repeated for disconnect switch 6
75BE
...Repeated for disconnect switch 7
75D3
...Repeated for disconnect switch 8
75E8
...Repeated for disconnect switch 9
75FD
...Repeated for disconnect switch 10
7612
...Repeated for disconnect switch 11
7627
...Repeated for disconnect switch 12
763C
...Repeated for disconnect switch 13
7651
...Repeated for disconnect switch 14
7666
...Repeated for disconnect switch 15
767B
...Repeated for disconnect switch 16
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60
User Programmable Pushbutton 1 Function
0 to 2
---
1
F109
2 (Disabled)
7B61
User Programmable Pushbutton 1 Top Line
---
---
---
F202
(none)
7B6B
User Programmable Pushbutton 1 On Text
---
---
---
F202
(none)
7B75
User Programmable Pushbutton 1 Off Text
---
---
---
F202
(none)
7B7F
User Programmable Pushbutton 1 Drop-Out Time
0 to 60
s
0.05
F001
0
7B80
User Programmable Pushbutton 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7B81
User Programmable Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
7B82
User Programmable Pushbutton 1 LED Operand
0 to 65535
---
1
F300
0
7B83
User Programmable Pushbutton 1 Autoreset Delay
0 to 600
s
0.05
F001
0
7B84
User Programmable Pushbutton 1 Autoreset Function
0 to 1
---
1
F102
0 (Disabled)
7B85
User Programmable Pushbutton 1 Local Lock
0 to 65535
---
1
F300
0
7B86
User Programmable Pushbutton 1 Message Priority
0 to 2
---
1
F220
0 (Disabled)
7B87
User Programmable Pushbutton 1 Remote Lock
0 to 65535
---
1
F300
0
7B88
User Programmable Pushbutton 1 Reset
0 to 65535
---
1
F300
0
7B89
User Programmable Pushbutton 1 Set
0 to 65535
---
1
F300
0
7B8A
User Programmable Pushbutton 1 Hold
0 to 10
s
0.1
F001
1
7B8B
...Repeated for User Programmable Pushbutton 2
7BB6
...Repeated for User Programmable Pushbutton 3
7BE1
...Repeated for User Programmable Pushbutton 4
7C0C
...Repeated for User Programmable Pushbutton 5
7C37
...Repeated for User Programmable Pushbutton 6
7C62
...Repeated for User Programmable Pushbutton 7
7C8D
...Repeated for User Programmable Pushbutton 8
7CB8
...Repeated for User Programmable Pushbutton 9
7CE3
...Repeated for User Programmable Pushbutton 10
7D0E
...Repeated for User Programmable Pushbutton 11
7D39
...Repeated for User Programmable Pushbutton 12
7D64
...Repeated for User Programmable Pushbutton 13
7D8F
...Repeated for User Programmable Pushbutton 14
7DBA
...Repeated for User Programmable Pushbutton 15
7DE5
...Repeated for User Programmable Pushbutton 16
Underfrequency (Read/Write Setting) (6 modules)
7E10
Underfrequency Function
0 to 1
---
1
F102
0 (Disabled)
7E11
Underfrequency 1 Block
0 to 65535
---
1
F300
0
7E12
Underfrequency 1 Minimum Current
0.1 to 1.25
pu
0.01
F001
10
7E13
Underfrequency 1 Pickup
20 to 65
Hz
0.01
F001
5950
7E14
Underfrequency 1 Pickup Delay
0 to 65.535
s
0.001
F001
2000
7E15
Underfrequency 1 Reset Delay
0 to 65.535
s
0.001
F001
2000
7E16
Underfrequency 1 Source
0 to 5
---
1
F167
0 (SRC 1)
Table B–9: MODBUS MEMORY MAP (Sheet 28 of 58)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...