5-248
G60 Generator Protection System
GE Multilin
5.9 TRANSDUCER INPUTS AND OUTPUTS
5 SETTINGS
5
It is recommended to use the G60 to configure the RRTD parameters. If the RRTDPC software is used to change the
RRTD settings directly (the application and type settings), then one of the following two operations is required for changes
to be reflected in the G60.
•
Cycle power to G60.
•
Break then re-establish the communication link between the RRTD unit and the G60. This will cause the
RRTD COMM
FAIL
operand to be asserted then de-asserted.
b) REMOTE RTDS 1 THROUGH 12
PATH: SETTINGS
ÖØ
TRANSDUCER I/O
ÖØ
RRTD INPUTS
ÖØ
RRTD RTD 1(12)
The remote RTD inputs convert values of input resistance into temperature for further operations. These inputs are
intended to be connected to any of the RTD types in common use. Specific hardware details are contained in chapter 3.
On power up, the G60 reads and saves all application and type settings from the RRTD. This synchronizes the RRTD and
G60. Any changes to RRTD settings (function, application, or type) from the G60 interface are immediately reflected in the
RRTD. The following rules are followed.
•
If the
RRTD 1 FUNCTION
setting is “Enabled”, then the
RRTD 1 APPLICATION
setting value will be written to RRTD device.
•
If the
RRTD 1 FUNCTION
setting is “Disabled”, then
RRTD1 APPLICATION
setting value is set as “None”.
•
If the
RRTD 1 APPLICATION
or
RRTD 1 TYPE
settings are changes, then these settings are immediately written to the
RRTD device.
RRTD 1
RRTD 1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
RRTD 1 ID:
RRTD 1
Range: Up to 20 alphanumeric characters
MESSAGE
RRTD 1 TYPE:
100
Ω
Nickel
Range: 100
Ω
Nickel, 10
Ω
Copper, 100
Ω
Platinum,
120
Ω
Nickel
MESSAGE
RRTD 1
APPLICATION: Bearing
Range: None, Stator, Bearing, Ambient, Group 1,
Group 2
MESSAGE
RRTD 1 ALARM
TEMPERATURE: 130°C
Range: 1 to 200°C in steps of 1
MESSAGE
RRTD 1 ALARM
PKP DELAY: 5 s
Range: 5 to 600 s in steps of 5
MESSAGE
RRTD 1 TRIP
TEMPERATURE: 130°C
Range: 1 to 200°C in steps of 1
MESSAGE
RRTD 1 TRIP
PKP DELAY: 5 s
Range: 5 to 600 s in steps of 5
MESSAGE
RRTD 1 TRIP
RST DELAY: 5 s
Range: 5 to 600 s in steps of 5
MESSAGE
RRTD 1 TRIP VOTING:
None
Range: None, Group, Remote RTD 1, Remote RTD 2,...,
Remote RTD 12
MESSAGE
RRTD 1 OPEN:
None
Range: None, Alarm, Block
MESSAGE
RRTD 1 BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
RRTD 1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
RRTD 1 EVENTS:
Disabled
Range: Disabled, Enabled
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...