5-188
G60 Generator Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
5.6.13 LOSS OF EXCITATION
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
LOSS OF EXCITATION
The operating characteristic is shaped out of two offset mho circles shifted down along the imaginary axis as shown below.
Figure 5–105: LOSS OF EXCITATION OPERATING CHARACTERISTICS
LOSS OF
EXCITATION
LOSS OF EXCITATION
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
LOSS OF EXCITATION
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
LOSS OF EXCITATION
CENTER 1: 10.00 ohm
Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
LOSS OF EXCITATION
RADIUS 1: 8.00 ohm
Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
EXCITATION V SUPV 1:
Enabled
Range: Disabled, Enabled
MESSAGE
LOSS OF EXCITATION
PKP DELAY1: 0.050 s
Range: 0.000 to 65.535 s in steps of 0.01
MESSAGE
LOSS OF EXCITATION
CENTER 2: 12.00 ohm
Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
LOSS OF EXCITATION
RADIUS 2: 10.00 ohm
Range: 0.10 to 300.00 ohms in steps of 0.01
MESSAGE
LOSS OF EXCITATION
V SUPV 2: Enabled
Range: Disabled, Enabled
MESSAGE
LOSS OF EXCITATION
PKP DELAY2: 0.500 s
Range: 0.000 to 65.535 s in steps of 0.01
MESSAGE
LOSS OF EXCITATION
UV SUPV: 0.700 pu
Range: 0.000 to 1.250 pu in steps of 0.001
MESSAGE
LOSS OF EXCIT BLK:
Off
Range: FlexLogic™ operand
MESSAGE
LOSS OF EXCITATION
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
LOSS OF EXCITATION
EVENTS: Disabled
Range: Disabled, Enabled
830711A1.CDR
C1
Zb
Xd
R
C1
R1
C2
R2
Zb
X’d
Xd
= Center of element 1 = (Zb + X’d) / 2
= Radius of element 1 = Zb / 2
= Center of element 2 = (Xd + X’d) / 2
= Radius of element 2 = Xd / 2
= Base impedance of the machine
= Transient reactance of the machine
= Synchronous reactance of the machine
X
X’d 2
R1
R2
C2
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...