5-162
G60 Generator Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
Figure 5–83: NEUTRAL DIRECTIONAL OVERCURRENT LOGIC
5.6.8 GROUND CURRENT
a) MAIN MENU
PATH: SETTINGS
Ø
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
GROUND CURRENT
The G60 relay contains one Ground Time Overcurrent, one Ground Instantaneous Overcurrent, and four Restricted Ground
Fault elements. Refer to Inverse Time Overcurrent Characteristics on page 5–144 for additional information.
GROUND CURRENT
GROUND TOC1
MESSAGE
GROUND IOC1
MESSAGE
RESTRICTED GROUND
FAULT 1
↓
MESSAGE
RESTRICTED GROUND
FAULT 4
FLEXLOGIC OPERAND
FLEXLOGIC OPERAND
SETTING
SETTING
SETTING
SETTING
SETTINGS
SETTING
SETTING
NEUTRAL DIR OC1
FUNCTION:
NEUTRAL DIR OC1
SOURCE:
NEUTRAL DIR OC1 POL
VOLT:
NEUTRAL DIR OC1 OP
CURR:
NEUTRAL DIR OC1
POLARIZING:
NEUTRAL DIR OC1 BLK:
NEUTRAL DIR OC1 FWD
LIMIT ANGLE:
NEUTRAL DIR OC1 FWD
ECA:
NEUTRAL DIR OC1 REV
LIMIT ANGLE:
NEUTRAL DIR OC1
OFFSET:
NEUTRAL DIR OC1 FWD
PICKUP:
NEUTRAL DIR OC1 REV
PICKUP:
NEUTRAL DIR OC1 OP
CURR:
NEUTRAL DIR OC1 OP
CURR:
NEUTRAL DIR OC1 FWD
NEUTRAL DIR OC1 REV
Disabled=0
Measured VX
Voltage
Calculated V_0
}
}
Current
Ground Crt (IG)
Zero Seq Crt (I_0)
Dual
NOTE:
1) CURRENT POLARIZING IS POSSIBLE ONLY IN RELAYS WITH
THE GROUND CURRENT INPUTS CONNECTED TO
AN ADEQUATE CURRENT POLARIZING SOURCE
2) GROUND CURRENT CAN NOT BE USED FOR POLARIZATION
AND OPERATION SIMULTANEOUSLY
3) POSITIVE SEQUENCE RESTRAINT IS NOT APPLIED WHEN
_1 IS BELOW 0.8pu
I
827077AB.CDR
Off=0
Enabled=1
AND
AND
AND
AND
AND
AND
AND
OR
OR
OR
OR
I
G 0.05 pu
3( _0 - K _1 ) PICKUP
I
I
3( _0 - K _1 ) PICKUP
I
I
I
G PICKUP
I
G PICKUP
Voltage Polarization
Current Polarization
-3V_0
3I_0
FWD
FWD
FWD
REV
REV
REV
RUN
RUN
RUN
OR
OR
RUN
1.25 cy
1.5 cy
NEUTRAL DIR OC1 POS-
SEQ RESTRAINT:
NEUTRAL DIR OC1 POS-
SEQ RESTRAINT:
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...