GE Multilin
G60 Generator Protection System
5-117
5 SETTINGS
5.5 FLEXLOGIC™
5
= Virt Op 3
Virt Op 4 On
Virt Op 1 On
Virt Op 2 On
Virt Ip 1 On
DIG ELEM 1 PKP
XOR(2)
Virt Op 3 On
OR(4)
LATCH (S,R)
Virt Op 3 On
TIMER 1
Cont Ip H1c On
OR(3)
TIMER 2
= Virt Op 4
END
In the expression above, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a
form of feedback, in this case, used to create a seal-in effect with the latch, and is correct.
8.
The logic should always be tested after it is loaded into the relay, in the same fashion as has been used in the past.
Testing can be simplified by placing an "END" operator within the overall set of FlexLogic™ equations. The equations
will then only be evaluated up to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.
5.5.5 FLEXLOGIC™ EQUATION EDITOR
PATH: SETTINGS
ÖØ
FLEXLOGIC
Ö
FLEXLOGIC EQUATION EDITOR
There are 512 FlexLogic™ entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" Ele-
ment is selected as a FlexLogic™ entry, the associated state flag will never be set to ‘1’. The ‘+/–‘ key may be used when
editing FlexLogic™ equations from the keypad to quickly scan through the major parameter types.
5.5.6 FLEXLOGIC™ TIMERS
PATH: SETTINGS
ÖØ
FLEXLOGIC
ÖØ
FLEXLOGIC TIMERS
Ö
FLEXLOGIC TIMER 1(32)
There are 32 identical FlexLogic™ timers available. These timers can be used as operators for FlexLogic™ equations.
•
TIMER 1 TYPE:
This setting is used to select the time measuring unit.
•
TIMER 1 PICKUP DELAY:
Sets the time delay to pickup. If a pickup delay is not required, set this function to "0".
FLEXLOGIC
EQUATION EDITOR
FLEXLOGIC ENTRY
1:
END
Range: FlexLogic™ operands
MESSAGE
FLEXLOGIC ENTRY
2:
END
Range: FlexLogic™ operands
↓
MESSAGE
FLEXLOGIC ENTRY 512:
END
Range: FlexLogic™ operands
FLEXLOGIC
TIMER 1
TIMER 1
TYPE: millisecond
Range: millisecond, second, minute
MESSAGE
TIMER 1
PICKUP
DELAY: 0
Range: 0 to 60000 in steps of 1
MESSAGE
TIMER 1
DROPOUT
DELAY: 0
Range: 0 to 60000 in steps of 1
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...