5 SETTINGS
5.4 SYSTEM SETUP
5
Figure 5–36: VOLTAGE TRIGGER SCHEME LOGIC
i) CURRENT TRIGGERING
PATH: SETTINGS
ÖØ
SYSTEM SETUP
ÖØ
PHASOR MEASUREMENT...
ÖØ
PMU 1 TRIGGERING
ÖØ
PMU 1 CURRENT TRIGGER
This element responds to elevated current. The trigger responds to the phase current signal of the phasor measurement
unit (PMU) source. All current channel (A, B, and C) are processed independently and could trigger the recorder.
•
PMU 1 CURR TRIGGER PICKUP
: This setting specifies the pickup threshold for the overcurrent trigger, in per unit of
the PMU source. A value of 1 pu is a nominal primary current. The comparator applies a 3% hysteresis.
•
PMU 1 CURR TRIGGER PKP TIME
: This setting could be used to filter out spurious conditions and avoid unneces-
sary triggering of the recorder.
•
PMU 1 CURR TRIGGER DPO TIME
: This setting could be used to extend the trigger after the situation returned to nor-
mal. This setting is of particular importance when using the recorder in the forced mode (recording as long as the trig-
gering condition is asserted).
PMU 1 CURRENT
TRIGGER
PMU 1 CURR TRIGGER
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
PMU 1 CURR TRIGGER
PICKUP: 1.800 pu
Range: 0.100 to 30.000 pu in steps of 0.001
MESSAGE
PMU 1 CURR TRIGGER
PKP TIME: 0.10 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PMU 1 CURR TRIGGER
DPO TIME: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PMU 1 CURR TRIG BLK:
Off
Range: FlexLogic™ operand
MESSAGE
PMU 1 CURR TRIGGER
TARGET: Self-Reset
Range: Self-Reset, Latched, Disabled
MESSAGE
PMU 1 CURR TRIGGER
EVENTS: Disabled
Range: Enabled, Disabled
847005A1.CDR
SETTINGS
PMU 1 VOLT TRIGGER
FUNCTION:
Enabled = 1
PMU 1 VOLT TRIG BLK:
Off = 0
SETTINGS
PMU 1 SIGNAL
SOURCE:
AND
SETTINGS
PMU 1 VOLT TRIGGER LOW-VOLT:
PMU 1 VOLT TRIGGER HIGH-VOLT:
RUN
SETTINGS
PMU 1 VOLT TRIGGER PKP TIME:
PMU 1 VOLT TRIGGER DPO TIME:
t
PKP
t
DPO
FLEXLOGIC OPERAND
PMU 1 VOLT TRIGGER
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER
PMU 1 ROCOF TRIGGER
SETTING
PMU 1 USER TRIGGER:
Off = 0
OR
FLEXLOGIC OPERAND
PMU 1 TRIGGERED
VT CONNECTION:
WYE
DELTA
VA
VAB
VB
VBC
VC
VCA
(0.1pu < V < LOW-VOLT) OR
(V > HIGH-VOLT)
(0.1pu < V < LOW-VOLT) OR
(V > HIGH-VOLT)
(0.1pu < V < LOW-VOLT) OR
(V > HIGH-VOLT)
OR
to STAT bits of
the data frame
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...