GE Multilin
G60 Generator Protection System
5-45
5 SETTINGS
5.2 PRODUCT SETUP
5
Refer to the
Control of setting groups
example in the
Control elements
section of this chapter for group activation.
5.2.11 USER-PROGRAMMABLE SELF TESTS
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
USER-PROGRAMMABLE SELF TESTS
All major self-test alarms are reported automatically with their corresponding FlexLogic™ operands, events, and targets.
Most of the minor alarms can be disabled if desired.
When in the “Disabled” mode, minor alarms will not assert a FlexLogic™ operand, write to the event recorder, or display
target messages. Moreover, they will not trigger the
ANY MINOR ALARM
or
ANY SELF-TEST
messages. When in the “Enabled”
mode, minor alarms continue to function along with other major and minor alarms. Refer to the
Relay self-tests
section in
chapter 7 for additional information on major and minor self-test alarms.
To enable the Ethernet switch failure function, ensure that the
ETHERNET SWITCH FAIL FUNCTION
is “Enabled” in this
menu.
Table 5–4: RECOMMENDED SETTINGS FOR USER-PROGRAMMABLE LEDS
SETTING
PARAMETER
SETTING
PARAMETER
LED 1 operand
SETTING GROUP ACT 1
LED 13 operand
Off
LED 2 operand
SETTING GROUP ACT 2
LED 14 operand
Off
LED 3 operand
SETTING GROUP ACT 3
LED 15 operand
Off
LED 4 operand
SETTING GROUP ACT 4
LED 16 operand
Off
LED 5 operand
SETTING GROUP ACT 5
LED 17 operand
SYNC 1 SYNC OP
LED 6 operand
SETTING GROUP ACT 6
LED 18 operand
SYNC 2 SYNC OP
LED 7 operand
Off
LED 19 operand
Off
LED 8 operand
Off
LED 20 operand
Off
LED 9 operand
Off
LED 21 operand
Off
LED 10 operand
Off
LED 22 operand
Off
LED 11 operand
Off
LED 23 operand
Off
LED 12 operand
Off
LED 24 operand
Off
USER-PROGRAMMABLE
SELF TESTS
DIRECT RING BREAK
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
DIRECT DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units equipped with
Direct Input/Output module.
MESSAGE
REMOTE DEVICE OFF
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
MESSAGE
PRI. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with a primary fiber port.
MESSAGE
SEC. ETHERNET FAIL
FUNCTION: Disabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with a redundant fiber port.
MESSAGE
BATTERY FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
SNTP FAIL
FUNCTION: Enabled
Range: Disabled, Enabled. Valid for units that contain a
CPU with Ethernet capability.
MESSAGE
IRIG-B FAIL
FUNCTION: Enabled
Range: Disabled, Enabled.
MESSAGE
ETHERNET SWITCH FAIL
FUNCTION: Disabled
Range: Disabled, Enabled.
NOTE
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...