GE Multilin
G60 Generator Protection System
5-17
5 SETTINGS
5.2 PRODUCT SETUP
5
c) NETWORK
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
NETWORK
These messages appear only if the G60 is ordered with an Ethernet card.
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, and HTTP protocols. The
NSAP address is used with the IEC 61850 protocol over the OSI (CLNP/TP4) stack only. Each network protocol has a set-
ting for the TCP/UDP port number. These settings are used only in advanced network configurations and should normally
be left at their default values, but may be changed if required (for example, to allow access to multiple UR-series relays
behind a router). By setting a different
TCP/UDP PORT NUMBER
for a given protocol on each UR-series relay, the router can
map the relays to the same external IP address. The client software (EnerVista UR Setup, for example) must be configured
to use the correct port number if these settings are used.
When the NSAP address, any TCP/UDP port number, or any user map setting (when used with DNP) is changed, it
will not become active until power to the relay has been cycled (off-on).
Do not set more than one protocol to the same
TCP/UDP PORT NUMBER
, as this will result in unreliable opera-
tion of those protocols.
d) MODBUS PROTOCOL
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
COMMUNICATIONS
ÖØ
MODBUS PROTOCOL
The serial communication ports utilize the Modbus protocol, unless configured for DNP or IEC 60870-5-104 operation (see
descriptions below). This allows the EnerVista UR Setup software to be used. The UR operates as a Modbus slave device
only. When using Modbus protocol on the RS232 port, the G60 will respond regardless of the
MODBUS SLAVE ADDRESS
pro-
grammed. For the RS485 ports each G60 must have a unique address from 1 to 254. Address 0 is the broadcast address
which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same
address or conflicts resulting in errors will occur. Generally, each device added to the link should use the next higher
address starting at 1. Refer to Appendix B for more information on the Modbus protocol.
Changes to the
MODBUS TCP PORT NUMBER
setting will not take effect until the G60 is restarted.
NETWORK
IP ADDRESS:
0.0.0.0
Range: Standard IP address format
Not shown if CPU Type E is ordered.
MESSAGE
SUBNET IP MASK:
0.0.0.0
Range: Standard IP address format
Not shown if CPU Type E is ordered.
MESSAGE
GATEWAY IP ADDRESS:
0.0.0.0
Range: Standard IP address format
Not shown if CPU Type E is ordered.
MESSAGE
OSI NETWORK
ADDRESS (NSAP)
Range: Select to enter the
OSI NETWORK ADDRESS
.
Not shown if CPU Type E is ordered.
MESSAGE
ETHERNET OPERATION
MODE: Full-Duplex
Range: Half-Duplex, Full-Duplex
Not shown if CPU Type E or N is ordered.
MODBUS PROTOCOL
MODBUS SLAVE
ADDRESS: 254
Range: 1 to 254 in steps of 1
MESSAGE
MODBUS TCP PORT
NUMBER:
502
Range: 1 to 65535 in steps of 1
NOTE
WARNING
NOTE
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...