5-10
G60 Generator Protection System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
Proper passwords are required to enable each command or setting level access. A command or setting password consists
of 1 to 10 numerical characters and are initially programmed to “0”. The following procedure describes how the set the com-
mand or setting password.
1.
Enter the new password in the
Enter New Password
field.
2.
Re-enter the password in the
Confirm New Password
field.
3.
Click the
Change
button. This button will not be active until the new password matches the confirmation password.
4.
If the original password is not “0”, then enter the original password in the
Enter Password
field and click the
Send
Password to Device
button.
5.
The new password is accepted and a value is assigned to the
ENCRYPTED PASSWORD
item.
If a command or setting password is lost (or forgotten), consult the factory with the corresponding
Encrypted Password
value.
d) ACCESS SUPERVISION
PATH: SETTINGS
Ö
PRODUCT SETUP
Ö
SECURITY
ÖØ
ACCESS SUPERVISION
The following access supervision settings are available.
•
INVALID ATTEMPTS BEFORE LOCKOUT
: This setting specifies the number of times an incorrect password can be
entered within a three-minute time span before lockout occurs. When lockout occurs, the
LOCAL ACCESS DENIED
and
REMOTE ACCESS DENIED
FlexLogic™ operands are set to “On”. These operands are returned to the “Off” state upon
expiration of the lockout.
•
PASSWORD LOCKOUT DURATION
: This setting specifies the time that the G60 will lockout password access after
the number of invalid password entries specified by the
INVALID ATTEMPS BEFORE LOCKOUT
setting has occurred.
The G60 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing
a password-protected level of the relay (either settings or commands), the
UNAUTHORIZED ACCESS
FlexLogic™ operand is
asserted. The operand can be programmed to raise an alarm via contact outputs or communications. This feature can be
used to protect against both unauthorized and accidental access attempts.
ACCESS
SUPERVISION
ACCESS LEVEL
TIMEOUTS
MESSAGE
INVALID ATTEMPTS
BEFORE LOCKOUT: 3
Range: 2 to 5 in steps of 1
MESSAGE
PASSWORD LOCKOUT
DURATION: 5 min
Range: 5 to 60 minutes in steps of 1
Summary of Contents for G60 UR Series
Page 2: ......
Page 4: ......
Page 12: ...xii G60 Generator Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 132: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 392: ...5 260 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 418: ...6 26 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 482: ...A 12 G60 Generator Protection System GE Multilin A 1 PARAMETER LISTS APPENDIXA A ...
Page 604: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 616: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 634: ...x G60 Generator Protection System GE Multilin INDEX ...