255
Moderate Response
Manual Tuning Guideline
without changing the value of 0 in X_BST_ON_THRESHOLD[1][2] and
X_BST_OFF_THRESHOLD[1][2]. First, try to input a negative value of half that
of BOOST_VALUE [1] [2], and if necessary, increment or decrement the value by
1.
❑
If necessary, increment or decrement the value for SERVO_GAIN by 30.
Improving the Stabilization Time
1. Decrease the value for SERVO_RESET to improve the capability of tracking the
target value.
2. Verify the 10% step response and decrement the value by 3.
Improving the Response Time
❑
If you input a value in a small step of 5% or less and response is slow, increment
the value for SERVO_GAIN by 30.
❑
If necessary, increment or decrement the value for BOOST_VALUE [1] [2] and
X_BOOST_VALUE [1] [2] by 1, respectively.
Checking Hunting Operation
Input a value in a large step of approx. 80% to ensure the hunting operation does not
occur. If the hunting operation does occur, decrease the value for SERVO_GAIN to 2/3
or 1/2 of the originally entered value. (5) After tuning the control parameters, re-check
each parameter if necessary.
Moderate Response
Figure 87
Moderate Response
Improving the stabilization time
1. Decrease the value for SERVO_RESET to improve the capability of tracking the
target value.
2. Verify the 10% step response and decrement the value by 3.
Summary of Contents for FVP110
Page 14: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 22: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 48: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 50: ...FVP 110 Fieldbus Valve Positioner Manual 34 GE Energy Block Diagram Figure 14 Block Diagram ...
Page 74: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 88: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 97: ...81 Dimensions Standard Specifications Dimensions Figure 46 Single Acting Actuator Dimensions ...
Page 99: ...83 Dimensions Standard Specifications Figure 48 Terminal Configuration ...
Page 100: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 115: ...99 View Object Configuration Table 11 View Object for Transducer Block continued ...
Page 117: ...101 View Object Configuration Table 18 View Object for AO Function Block ...
Page 119: ...103 View Object Configuration Table 20 View Object for OS Function Block ...
Page 121: ...105 View Object Configuration Table 22 View Object for Resource Block ...
Page 124: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 130: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 138: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 156: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 168: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 238: ...FVP 110 Fieldbus Valve Positioner Manual 222 GE Energy Table 72 LM Parameter Part List ...
Page 239: ...223 LM Parameter List Link Master Functions ...
Page 246: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 262: ...FVP 110 Fieldbus Valve Positioner Manual 246 GE Energy Table 85 Download Error Codes ...
Page 265: ...249 Comments on System Network Software Download Table 88 DOMAIN_DESCRIPTOR ...
Page 266: ...FVP 110 Fieldbus Valve Positioner Manual 250 GE Energy Table 89 DOMAIN_HEADER ...
Page 288: ...FVP 110 Fieldbus Valve Positioner Manual This page intentionally left blank ...
Page 289: ...273 H Customer Maintenance Parts List ...
Page 290: ...FVP 110 Fieldbus Valve Positioner Manual 274 GE Energy ...
Page 291: ......