Critical Power
Modifications reserved
Page 29/69
GE_UPS_ISG_TLE_SUL_M62_1M0_2US_V010.docx
Installation Guide
TLE Series 625 - 750 - 1000 UL S2
4.7.3
Control cables interconnection
WARNING !
All the cables interconnection must be performed by QUALIFIED SERVICE
PERSONNEL only.
TLE Series 625 & 750 Control cables interconnection
Fig. 4.7.3-1 TLE Series 625 & 750 – Control cables interconnection
Pos.
Connection
From
Connecting to
1
XD1 – HAN Connector male (46 poles)
“Power Section cabinet”
“In/Out Section cabinet”
2
XD2 - HAN Connector male (32 poles)
“Power Section cabinet”
“In/Out Section cabinet”
3
XTR2A - Connector
“Power Section cabinet”
“In/Out Section cabinet”
XTR2 Connector
Fig. 4.7.3-2 Connection of hearting connectors (HAN connectors)
NOTE:
All these connections must be performed by
QUALIFIED SERVICE PERSONNEL only.
Proper dressing needs to be done for each cable
assembly in order to reduce the stress.
All the cables must be sufficiently (at least 4”/10 cm)
away from all live parts.
Cable binders used to support the wiring must NOT be
overly tightened.
XD1
(46 poles)
XD2
(32 poles)
XD1
(46 poles)
XD2
(32 poles)
XD2 Connector (32 poles)
1
2
In/Out Section cabinet
Power Section cabinet
TLES_UL_750_S2_U
PS connection cabin
ets_GE_03US
1
2
XD1 Connector (46 poles)