GE Multilin
F60 Feeder Protection System
B-25
APPENDIX B
B.4 MEMORY MAPPING
B
47A7
Synchrocheck 1 Dead Source Select
0 to 5
---
1
F176
1 (LV1 and DV2)
47A8
Synchrocheck 1 Dead V1 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
47A9
Synchrocheck 1 Dead V2 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
47AA
Synchrocheck 1 Live V1 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
47AB
Synchrocheck 1 Live V2 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
47AC
Synchrocheck 1 Target
0 to 2
---
1
F109
0 (Self-reset)
47AD
Synchrocheck 1 Events
0 to 1
---
1
F102
0 (Disabled)
47AE
Synchrocheck 1 Block
0 to 65535
---
1
F300
0
47AF
Synchrocheck 1 Frequency Hysteresis
0 to 0.1
Hz
0.01
F001
6
47B0
...Repeated for Synchrocheck 2
Demand (Read/Write Setting)
47D0
Demand Current Method
0 to 2
---
1
F139
0 (Thrm. Exponential)
47D1
Demand Power Method
0 to 2
---
1
F139
0 (Thrm. Exponential)
47D2
Demand Interval
0 to 5
---
1
F132
2 (15 MIN)
47D3
Demand Input
0 to 65535
---
1
F300
0
Demand (Read/Write Command)
47D4
Demand Clear Record
0 to 1
---
1
F126
0 (No)
Flexcurves A and B (Read/Write Settings)
4800
FlexCurve A (120 items)
0 to 65535
ms
1
F011
0
48F0
FlexCurve B (120 items)
0 to 65535
ms
1
F011
0
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
0 to 65535
---
1
F001
0
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
---
---
---
F202
“ “
4C0A
User-Definable Display 1 Bottom Line Text
---
---
---
F202
““
4C14
Modbus Addresses of Display 1 Items (5 items)
0 to 65535
---
1
F001
0
4C19
Reserved (7 items)
---
---
---
F001
0
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
4D60
...Repeated for User-Definable Display 12
4D80
...Repeated for User-Definable Display 13
4DA0
...Repeated for User-Definable Display 14
4DC0
...Repeated for User-Definable Display 15
4DE0
...Repeated for User-Definable Display 16
User Programmable Pushbuttons (Read/Write Setting) (12 modules)
4E00
User Programmable Pushbutton 1 Function
0 to 2
---
1
F109
2 (Disabled)
4E01
User Programmable Pushbutton 1 Top Line
---
---
---
F202
(none)
4E0B
User Programmable Pushbutton 1 On Text
---
---
---
F202
(none)
4E15
User Programmable Pushbutton 1 Off Text
---
---
---
F202
(none)
4E1F
User Programmable Pushbutton 1 Drop-Out Time
0 to 60
s
0.05
F001
0
4E20
User Programmable Pushbutton 1 Target
0 to 2
---
1
F109
0 (Self-reset)
4E21
User Programmable Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
4E22
User Programmable Pushbutton 1 LED Operand
0 to 65535
---
1
F300
0
4E23
User Programmable Pushbutton 1 Autoreset Delay
0 to 600
s
0.05
F001
0
4E24
User Programmable Pushbutton 1 Autoreset Function
0 to 1
---
1
F102
0 (Disabled)
4E25
User Programmable Pushbutton 1 Local Lock
0 to 65535
---
1
F300
0
Table B–9: MODBUS MEMORY MAP (Sheet 17 of 53)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for F60 UR Series
Page 2: ......
Page 4: ......
Page 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 48: ...2 18 F60 Feeder Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 126: ...4 30 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 354: ...5 228 F60 Feeder Protection System GE Multilin 5 9 TESTING 5 SETTINGS 5 ...
Page 382: ...6 28 F60 Feeder Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 398: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 414: ...A 14 F60 Feeder Protection System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 492: ...B 78 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 530: ...D 10 F60 Feeder Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIXD D ...
Page 542: ...E 12 F60 Feeder Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 558: ...x F60 Feeder Protection System GE Multilin INDEX ...