imagination at work
EntelliGuard
®
Digital Test Kit
User’s Guide
DEH-4568
Page 1: ...imagination at work EntelliGuard Digital Test Kit User s Guide DEH 4568 ...
Page 2: ...has an associated red LED that indicates the state of the switch If the LED is illuminated then switch is ON and firing the flux shifter to trip the breaker Disable Ground Fault Pressing this button will cause the trip unit GF protection to be temporarily disabled To enable the GF the switch and associated red LED must be turned off The GF switch has an associated red LED that indicates the state ...
Page 3: ...DB9 female cable This cable connects the Test Kit to a PC Part number 45 0314 from GC Electronics or equivalent Below is the connection diagram between the test kit and PC Test Kit DB 9 PC Comm port DB 9 2 2 3 3 5 5 EntelliGuard Trip Unit cable 6 ft SVGA VGA Monitor Extension Cable HD15M to HD15F This cable connects the Test Kit to EntelliGuard Trip Unit Part Number SPC20050 from SPC Technology or...
Page 4: ...eaker button The breaker will then open If trip unit fails to trip the breaker in this test remove the breaker from service and refer the trip unit to an authorized GE service representative Ground Fault Disable This feature should only be used when testing the breaker with the breaker disconnected from the source upstream breaker or switch open or breaker racked out This test is used when perform...