GEK – 106166B
44
Level 1
Level 2
Level 3
Description
Valid range
ENABLING
59P FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
81 U1 FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
81 U2 FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
81 U3 FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
VIEW
PROTECTION
SETTINGS
FUNCTION
ENABLING
81 U4
FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
CHANGE
PROTECT
SETTINGS
81 U5
FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
81 U6
FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
81 U7
FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
81 U8
FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
27P TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
59P TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
81 U1 TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
81 U2 TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
81 U3 TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
81 U4 TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
81 U5 TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
81 U6 TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
81 U7 TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
81 U8 TRIP
Allows to enable or to
disable the function
Enabled
/Disabled
T1, T2, T3
27P PICKUP
27P PICKUP
Undervoltage function
pickup
20 to 110 Vac in
steps of 0.01V
27P OPERATION
t
Undervoltage function time
delay
0 to 30 s in
steps of 0.01s
27P RESET t
Undervoltage function reset
time
0 a 1200 s in
steps of 1s
VIEW
PROTECTION
SETTINGS
T1, T2, T3
59P PICKUP
59P PICKUP
Overvoltage function pickup
value
50 to 220 Vac in
steps of 0.01V
CHANGE
PROTECT
SETTINGS
59P OPERATION
t
Overvoltage function time
delay
0 to 30 s in
steps of 0.01s
59P RESET t
Overvoltage function output
contacts reset time
0 to 30 s in
steps of 1s
T1, T2, T3 81
U1 PICKUP
FUNCTION TYPE
Setting for operation as
absolute threshold or as
frequency derivative
change rate
FREC / dF/dT
( Same for
the rest of
81 PICKUP
Underfrequency pickup
40 to 70 Hz in
steps of 0.01
Summary of Contents for DFF1000 Series
Page 3: ......
Page 7: ...GEK 106166B 4 ...
Page 23: ...GEK 106166B 20 ...
Page 29: ...GEK 106166B 26 ...
Page 35: ...GEK 106166B 32 ...
Page 43: ...GEK 106166B 40 ...
Page 52: ...GEK 106166B 49 Figure 1 External Connections for DFF1000 model ...
Page 55: ...GEK 106166B 52 Figure 4 Panel Mounting ...
Page 57: ...GEK 106166B 54 Figure 6 Dimensions ...