GEK – 106166B
43
Level 1
Level 2
Level 3
Description
Valid range
VIEW
PROTECTION
SETTINGS
GENERAL
SETTINGS
RELAY STATUS
It takes the relay out of
service
In service / Out
of service
CHANGE
PROTECT
SETTINGS
FREQUENCY
Nominal frequency
50/60 Hz
NAME
Alphanumeric string of 20
characters
NOMINAL
VOLTAGE
Nominal voltage
90 - 220 Vac in
1 Vac steps
INHIBITION
VOLTAGE
Frequency functions
voltage inhibition value
40- 110 % of
nominal voltage
in steps of 1%
NUMBER OF
SEMI-CYCLES
Number of semi-cycles for
the frequency units’
operation
3-20 in steps of
1
NUMBER OF
RESET CYCLES
Number of reset cycles for
the frequency units
measure
0-4 in steps of 1
PHASE PT
RATIO
PT phase ratio
1 - 4000 in steps
of 1
GROUND PT
RATIO
PT ground ratio
1 - 4000 en
Steps de 1
ACTIVE
TABLE
SETTINGS
ACTIVE TABLE
Allows active table change
1-3
OSCILLOGR
APHY MASK
TYPE OF
OSCILLO
Allows to change the type of
oscillo
NORMAL /
FREC
PREFAULT
CYCLES
Programmable number of
prefault cycles
2 - 10
81 U1 PICKUP
Allows oscillography trigger
YES/NO
81 U2 PICKUP
Allows oscillography trigger
YES/NO
81 U3 PICKUP
Allows oscillography trigger
YES/NO
VIEW
PROTECTION
SETTINGS
OSCILLOGR
APHY MASK
81 U4 PICKUP
Allows oscillography trigger
YES/NO
CHANGE
PROTECT
SETTINGS
81 U5 PICKUP
Allows oscillography trigger
YES/NO
81 U6 PICKUP
Allows oscillography trigger
YES/NO
81 U7 PICKUP
Allows oscillography trigger
YES/NO
81 U8 PICKUP
Allows oscillography trigger
YES/NO
81 U1 TRIP
Allows oscillography trigger
YES/NO
81 U2 TRIP
Allows oscillography trigger
YES/NO
81 U3 TRIP
Allows oscillography trigger
YES/NO
81 U4 TRIP
Allows oscillography trigger
YES/NO
81 U5 TRIP
Allows oscillography trigger
YES/NO
81 U6 TRIP
Allows oscillography trigger
YES/NO
81 U7 TRIP
Allows oscillography trigger
YES/NO
81 U8 TRIP
Allows oscillography trigger
YES/NO
27P PICKUP
Allows oscillography trigger
YES/NO
59P PICKUP
Allows oscillography trigger
YES/NO
INPUT TRIGGER
Allows oscillography trigger
YES/NO
COMMUNICATIO
N TRIGGER
Allows oscillography trigger
YES/NO
27P TRIP
Allows oscillography trigger
YES/NO
59P TRIP
Allows oscillography trigger
YES/NO
FUNCTION
27P FUNCTION
Allows to enable or to
disable the function
Enabled
/Disabled
Summary of Contents for DFF1000 Series
Page 3: ......
Page 7: ...GEK 106166B 4 ...
Page 23: ...GEK 106166B 20 ...
Page 29: ...GEK 106166B 26 ...
Page 35: ...GEK 106166B 32 ...
Page 43: ...GEK 106166B 40 ...
Page 52: ...GEK 106166B 49 Figure 1 External Connections for DFF1000 model ...
Page 55: ...GEK 106166B 52 Figure 4 Panel Mounting ...
Page 57: ...GEK 106166B 54 Figure 6 Dimensions ...