D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE
9–1
D485 Modbus to DeviceNet
Converter
Chapter 9: Application example
GE
Grid Solutions
Application example
Introduction
OVERVIEW
The chapter describes how to configure the D485 Modbus to DeviceNet Converter to allow
GE Multilin relays and meters to communicate on a DeviceNet network. The GE Multilin
MM2 Motor Manager 2 and PQMII Power Quality Meter are used as examples.
GE Multilin relays and meters support a very useful feature called the Modbus User
Map in their software. This feature can be used in configuring the D485 to reduce the
number of Modbus transactions and improve communication speed.
It is assumed that the reader is familiar with serial communication, DeviceNet networks,
and PLC architecture.
EQUIPMENT AND
DOCUMENTS
The examples in this chapter make use of the following equipment and documentation
•
D485 Modbus to DeviceNet Converter
•
RS485 cable to connect D485 to the relays/meters (MM2 and PQMII)
•
EnerVista P485/D485 Setup software with configuration cable
•
EDS file for the D485
•
standard DeviceNet cable with connectors
•
24 V DC power supply for the D485
•
PLC with DeviceNet master card
•
PQMII Power Quality meter and instruction manual (publication code GEK-106435D)
•
Enervista PQMII Setup software
•
MM2 relay and instruction manual (publication code GEK-106294B)
•
MM2PC software
Summary of Contents for D485
Page 32: ...3 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE DATA EXCHANGE ...
Page 46: ...4 14 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE SOFTWARE OVERVIEW ...
Page 52: ...5 6 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE COMMUNICATION MODEL ...
Page 92: ...9 20 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE APPLICATION EXAMPLE ...
Page 94: ...10 2 D485 MODBUS TO DEVICENET CONVERTER USER GUIDE MISCELLANEOUS ...