CB Watch 3 User Manual
v6.3 - May 2019
Page 51 of 100
separation time offset (ts-t1) which we input during the setup. It can be set differently per
pole but is usually the same.
HMI: Settings / Opening
Figure 72
–
Separation offset input
Figure 73
–
Opening operation timing diagram
Using either of these two methods, the arcing time can be calculated and shown for each
operation:
HMI: Measurements / last opening results
Figure 74
–
Arcing time
Arcing time alarm
To receive a warning when the breaker is not interrupting the arc fast enough and the
arcing time is too long, an alarm can be set against a maximum threshold:
HMI: Settings / Opening
Figure 75
–
Max arcing time threshold