MA-037 - CB Watch 3 Operating Manual
v7.0 - May 2020
Page 26 of 118
HMI: Settings/Opening and Settings/Closing
Figure 28
–
Initial setting of number of operations
An alarm can be set against both the number of opening and closing operations if they
exceed a set threshold. The threshold is set here.
HMI: Settings/Opening and Settings/Closing
Figure 29
–
Setting operation counter thresholds
This alarm can be used for maintenance purposes
HMI: Measurements/Alarms
Figure 30
–
Operation counter alarms
52a/52b contacts status
The 52a/52b auxiliary contacts are proximity switches that are there to reflect a direct
image of the circuit breaker position and indicate the status of the circuit breaker:
•
52a aux. contact:
is ON when CB is CLOSED and OFF when CB is OPEN
•
52b aux. contact:
is OFF when CB is CLOSED and ON when CB is OPEN
HMI: Measurements/Sensors
Figure 31
–
Auxiliary contact status
If for any one pole, the 52a and 52b contacts have the same value (like in example above)
for longer than the “pole discrepancy timeout” set, then a “Pole discrepancy” alarm is
raised. It alerts to the fact that there is a problem with the 52a and 52b contacts for one
pole and that the position of the CB for that pole might be incorrect.