D-2
C70 Capacitor Bank Protection and Control System
GE Multilin
D.1 IEC 60870-5-103
APPENDIX D
D
D.1.3 INTEROPERABILITY DOCUMENT
The boxes indicate the following:
– used in standard direction;
– not used.
1.
PHYSICAL LAYER
Electrical interface
EIA RS-485
32
Number of loads for one protection equipment
Optical interface
Glass fibre
Plastic fibre
F-SMA type connector
BFOC/2.5 type connector
Transmission speed
9600 bits/s
19200 bits/s
2.
LINK LAYER
There are no choices for the link layer.
3.
APPLICATION LAYER
Transmission mode for application data
Mode 1 (least significant octet first), as defined in 4.10 of IEC 60870-5-4, is used exclusively in this companion stan-
dard.
Common address of ASDU
One COMMON ADDRESS OF ASDU (identical with station address)
More than one COMMON ADDRESS OF ASDU
Selection of standard information numbers in monitor direction
System functions in monitor direction
INF Semantics
<0> End of general interrogation
<0> Time synchronization
<2> Reset FCB
<3> Reset CU
<4> Start/restart
<5> Power on
Status indications in monitor direction
INF Semantics
<16> Auto-recloser active
<17> Teleprotection active
<18> Protection active
<19> LED reset
<20> Monitor direction blocked
<21> Test mode
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...