GE Multilin
C70 Capacitor Bank Protection and Control System
B-45
APPENDIX B
B.4 MEMORY MAPPING
B
7FA9
Reserved (8 items)
0 to 65535
---
1
F001
0
7FB1
...Repeated for Auxiliary Overvoltage 2
7FC2
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
2 to 90
Hz
0.01
F001
0
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
-55 to 125
C
1
F002
-55
81C1
Reserved Register T2
-55 to 125
C
1
F002
125
81C2
Reserved Register T3
-2147483647 to
2147483647
---
1
F004
0
81C4
Reserved Register T4
0 to 4294967295
---
1
F003
0
81C6
Reserved Register T5
0 to 4294967295
---
1
F003
0
81C8
Reserved Register T6
0 to 4294967295
---
1
F003
0
81CA
Reserved Register T7
0 to 4294967295
---
1
F003
0
81CC
Reserved Register T8
0 to 4294967295
---
1
F003
0
Breaker Failure (Read/Write Grouped Setting)
8600
Breaker Failure 1 Function
0 to 1
---
1
F102
0 (Disabled)
8601
Breaker Failure 1 Mode
0 to 1
---
1
F157
0 (3-Pole)
8602
Breaker Failure 1 Source
0 to 5
---
1
F167
0 (SRC 1)
8603
Breaker Failure 1 Amp Supervision
0 to 1
---
1
F126
1 (Yes)
8604
Breaker Failure 1 Use Seal-In
0 to 1
---
1
F126
1 (Yes)
8605
Breaker Failure 1 Three Pole Initiate
0 to 4294967295
---
1
F300
0
8607
Breaker Failure 1 Block
0 to 4294967295
---
1
F300
0
8609
Breaker Failure 1 Phase Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860A
Breaker Failure 1 Neutral Amp Supv Pickup
0.001 to 30
pu
0.001
F001
1050
860B
Breaker Failure 1 Use Timer 1
0 to 1
---
1
F126
1 (Yes)
860C
Breaker Failure 1 Timer 1 Pickup
0 to 65.535
s
0.001
F001
0
860D
Breaker Failure 1 Use Timer 2
0 to 1
---
1
F126
1 (Yes)
860E
Breaker Failure 1 Timer 2 Pickup
0 to 65.535
s
0.001
F001
0
860F
Breaker Failure 1 Use Timer 3
0 to 1
---
1
F126
1 (Yes)
8610
Breaker Failure 1 Timer 3 Pickup
0 to 65.535
s
0.001
F001
0
8611
Breaker Failure 1 Breaker Status 1 Phase A/3P
0 to 4294967295
---
1
F300
0
8613
Breaker Failure 1 Breaker Status 2 Phase A/3P
0 to 4294967295
---
1
F300
0
8615
Breaker Failure 1 Breaker Test On
0 to 4294967295
---
1
F300
0
8617
Breaker Failure 1 Phase Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8618
Breaker Failure 1 Neutral Amp Hiset Pickup
0.001 to 30
pu
0.001
F001
1050
8619
Breaker Failure 1 Phase Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861A
Breaker Failure 1 Neutral Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
861B
Breaker Failure 1 Loset Time
0 to 65.535
s
0.001
F001
0
861C
Breaker Failure 1 Trip Dropout Delay
0 to 65.535
s
0.001
F001
0
861D
Breaker Failure 1 Target
0 to 2
---
1
F109
0 (Self-reset)
861E
Breaker Failure 1 Events
0 to 1
---
1
F102
0 (Disabled)
861F
Breaker Failure 1 Phase A Initiate
0 to 4294967295
---
1
F300
0
8621
Breaker Failure 1 Phase B Initiate
0 to 4294967295
---
1
F300
0
8623
Breaker Failure 1 Phase C Initiate
0 to 4294967295
---
1
F300
0
8625
Breaker Failure 1 Breaker Status 1 Phase B
0 to 4294967295
---
1
F300
0
8627
Breaker Failure 1 Breaker Status 1 Phase C
0 to 4294967295
---
1
F300
0
8629
Breaker Failure 1 Breaker Status 2 Phase B
0 to 4294967295
---
1
F300
0
862B
Breaker Failure 1 Breaker Status 2 Phase C
0 to 4294967295
---
1
F300
0
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
0 to 4294967295
---
1
F300
0
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
0 to 1
---
1
F102
0 (Disabled)
8A01
Digital Element 1 Name
---
---
---
F203
“Dig Element 1“
Table B–10: MODBUS MEMORY MAP (Sheet 37 of 65)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...