GE Multilin
C70 Capacitor Bank Protection and Control System
6-5
6 ACTUAL VALUES
6.2 STATUS
6
6.2.7 REMOTE DEVICES
a) STATUS
PATH: ACTUAL VALUES
STATUS
REMOTE DEVICES STATUS
The present state of the programmed remote devices is shown here. The
ALL REMOTE DEVICES ONLINE
message indicates
whether or not all programmed remote devices are online. If the corresponding state is "No", then at least one required
remote device is not online.
b) STATISTICS
PATH: ACTUAL VALUES
STATUS
REMOTE DEVICES STATISTICS
REMOTE DEVICE 1(16)
Statistical data (two types) for up to 16 programmed remote devices is shown here.
The
STNUM
number is obtained from the indicated remote device and increments whenever a change of state of at least
one item occurs in the GSSE/GOOSE message. The
SQNUM
number is obtained from the indicated remote device and
increments whenever a GSSE/GOOSE message, without a state change, is sent. When the GSSE/GOOSE message
trasmits a state change, the
SQNUM
resets to 0. This number rolls over to zero when a count of 4,294,967,295 is incre-
mented.
6.2.8 DIGITAL COUNTERS
PATH: ACTUAL VALUES
STATUS
DIGITAL COUNTERS
DIGITAL COUNTERS Counter 1(8)
The present status of the eight digital counters is shown here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label will also appear). Also included, is the date and
time stamp for the frozen count. The
COUNTER 1 MICROS
value refers to the microsecond portion of the time stamp.
REMOTE DEVICES
STATUS
All REMOTE DEVICES
ONLINE: No
Range: Yes, No
MESSAGE
REMOTE DEVICE 1
STATUS: Offline
Range: Online, Offline
MESSAGE
REMOTE DEVICE 2
STATUS: Offline
Range: Online, Offline
↓
MESSAGE
REMOTE DEVICE 16
STATUS: Offline
Range: Online, Offline
REMOTE DEVICE 1
REMOTE DEVICE 1
StNum: 0
MESSAGE
REMOTE DEVICE 1
SqNum: 0
DIGITAL COUNTERS
Counter 1
Counter 1
ACCUM:
0
MESSAGE
Counter 1
FROZEN:
0
MESSAGE
Counter 1
FROZEN:
YYYY/MM/DD HH:MM:SS
MESSAGE
Counter 1
MICROS:
0
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...