GE Multilin
C70 Capacitor Bank Protection and Control System
5-217
5 SETTINGS
5.7 CONTROL ELEMENTS
5
Figure 5–97: TIME OF DAY TIMER LOGIC
5.7.6 CAPACITOR CONTROL
PATH: SETTINGS
CONTROL ELEMENTS
CAPACITOR CONTROL
CAPACITOR CONTROL 1(4)
CAPACITOR CONTROL 1
CAP 1 CTRL FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
CAP 1 SET REMOTE 1:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 SET REMOTE 2:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 SET LOCAL 1:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 SET LOCAL 2:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 RMT CTRL EN:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 LCL CTRL EN:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 RMT SET AUTO:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 LCL SET AUTO:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 RMT SET MAN:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 LCL SET MAN:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 TRIP 1:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 TRIP 2:
Off
Range: FlexLogic operand
MESSAGE
CAP 1 TRIP 3:
Off
Range: FlexLogic operand
842021A1.CDR
SETTING
TIME OF DAY TIMER 1
FUNCTION:
Enabled
Disabled
REAL-TIME CLOCK
time of day
SNTP
IRIG-B
SETTING
TIME OF DAY TIMER 1
START TIME:
TIME OF DAY TIMER 1
STOP TIME:
time >= START
time >= STOP
START > STOP
XOR
XOR
AND
AND
0
1 s
0
1 s
FLEXLOGIC OPERANDS
TIME OF DAY 1 START
TIME OF DAY 1 ON
TIME OF DAY 1 STOP
AND
Summary of Contents for C70
Page 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Page 394: ...5 270 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 676: ...E 10 C70 Capacitor Bank Protection and Control System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 698: ...H 8 C70 Capacitor Bank Protection and Control System GE Multilin H 3 WARRANTY APPENDIX H H ...