5-150
C60 Breaker Protection System
GE Multilin
5.5 FLEXLOGIC
5 SETTINGS
5
ELEMENT:
Digital elements
Dig Element 1 PKP
Dig Element 1 OP
Dig Element 1 DPO
Digital Element 1 is picked up
Digital Element 1 is operated
Digital Element 1 is dropped out
Dig Element 2 to 48
Same set of operands as shown for Dig Element 1
ELEMENT:
Sensitive directional
power
DIR POWER 1 STG1 PKP
DIR POWER 1 STG2 PKP
DIR POWER 1 STG1 DPO
DIR POWER 1 STG2 DPO
DIR POWER 1 STG1 OP
DIR POWER 1 STG2 OP
DIR POWER 1 PKP
DIR POWER 1 DPO
DIR POWER 1 OP
Stage 1 of the directional power element 1 has picked up
Stage 2 of the directional power element 1 has picked up
Stage 1 of the directional power element 1 has dropped out
Stage 2 of the directional power element 1 has dropped out
Stage 1 of the directional power element 1 has operated
Stage 2 of the directional power element 1 has operated
The directional power element has picked up
The directional power element has dropped out
The directional power element has operated
DIR POWER 2
Same set of operands as DIR POWER 1
ELEMENT:
FlexElements
FxE 1 PKP
FxE 1 OP
FxE 1 DPO
FlexElement 1 has picked up
FlexElement 1 has operated
FlexElement 1 has dropped out
FxE 2 to 8
Same set of operands as shown for FxE 1
ELEMENT:
Ground
instantaneous
overcurrent
GROUND IOC1 PKP
GROUND IOC1 OP
GROUND IOC1 DPO
Ground instantaneous overcurrent 1 has picked up
Ground instantaneous overcurrent 1 has operated
Ground instantaneous overcurrent 1 has dropped out
GROUND IOC2 to 8
Same set of operands as shown for GROUND IOC 1
ELEMENT:
Ground time
overcurrent
GROUND TOC1 PKP
GROUND TOC1 OP
GROUND TOC1 DPO
Ground time overcurrent 1 has picked up
Ground time overcurrent 1 has operated
Ground time overcurrent 1 has dropped out
GROUND TOC2 to 4
Same set of operands as shown for GROUND TOC1
ELEMENT
Non-volatile latches
LATCH 1 ON
LATCH 1 OFF
Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latch 1 is OFF (Logic = 0)
LATCH 2 to 16
Same set of operands as shown for LATCH 1
ELEMENT:
Neutral
instantaneous
overcurrent
NEUTRAL IOC1 PKP
NEUTRAL IOC1 OP
NEUTRAL IOC1 DPO
Neutral instantaneous overcurrent 1 has picked up
Neutral instantaneous overcurrent 1 has operated
Neutral instantaneous overcurrent 1 has dropped out
NEUTRAL IOC2 to 8
Same set of operands as shown for NEUTRAL IOC1
ELEMENT:
Neutral overvoltage
NEUTRAL OV1 PKP
NEUTRAL OV1 DPO
NEUTRAL OV1 OP
Neutral overvoltage element 1 has picked up
Neutral overvoltage element 1 has dropped out
Neutral overvoltage element 1 has operated
NEUTRAL OV2 to 3
Same set of operands as shown for NEUTRAL OV1
ELEMENT:
Neutral time
overcurrent
NEUTRAL TOC1 PKP
NEUTRAL TOC1 OP
NEUTRAL TOC1 DPO
Neutral time overcurrent 1 has picked up
Neutral time overcurrent 1 has operated
Neutral time overcurrent 1 has dropped out
NEUTRAL TOC2 to 6
Same set of operands as shown for NEUTRAL TOC1
ELEMENT:
Open pole detector
OPEN POLE OP
Ф
A
OPEN POLE OP
Ф
B
OPEN POLE OP
Ф
C
OPEN POLE OP
Open pole condition is detected in phase A
Open pole condition is detected in phase B
Open pole condition is detected in phase C
Open pole detector is operated
ELEMENT:
Synchrophasor
phasor data
concentrator
PDC NETWORK CNTRL 1
PDC NETWORK CNTRL 2
↓
PDC NETWORK CNTRL 16
Phasor data concentrator asserts control bit 1 as received via the network
Phasor data concentrator asserts control bit 2 as received via the network
↓
Phasor data concentrator asserts control bit 16 as received via the network
ELEMENT:
Phase
instantaneous
overcurrent
PHASE IOC1 PKP
PHASE IOC1 OP
PHASE IOC1 DPO
PHASE IOC1 PKP A
PHASE IOC1 PKP B
PHASE IOC1 PKP C
PHASE IOC1 OP A
PHASE IOC1 OP B
PHASE IOC1 OP C
PHASE IOC1 DPO A
PHASE IOC1 DPO B
PHASE IOC1 DPO C
At least one phase of phase instantaneous overcurrent 1 has picked up
At least one phase of phase instantaneous overcurrent 1 has operated
All phases of phase instantaneous overcurrent 1 have dropped out
Phase A of phase instantaneous overcurrent 1 has picked up
Phase B of phase instantaneous overcurrent 1 has picked up
Phase C of phase instantaneous overcurrent 1 has picked up
Phase A of phase instantaneous overcurrent 1 has operated
Phase B of phase instantaneous overcurrent 1 has operated
Phase C of phase instantaneous overcurrent 1 has operated
Phase A of phase instantaneous overcurrent 1 has dropped out
Phase B of phase instantaneous overcurrent 1 has dropped out
Phase C of phase instantaneous overcurrent 1 has dropped out
PHASE IOC2 to 8
Same set of operands as shown for PHASE IOC1
Table 5–18: C60 FLEXLOGIC OPERANDS (Sheet 3 of 7)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Summary of Contents for C60
Page 10: ...x C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 30: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 420: ...5 284 C60 Breaker Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 466: ...8 4 C60 Breaker Protection System GE Multilin 8 1 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 478: ...9 12 C60 Breaker Protection System GE Multilin 9 6 DISPOSAL 9 MAINTENANCE 9 ...
Page 492: ...A 14 C60 Breaker Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 648: ...E 10 C60 Breaker Protection System GE Multilin E 1 OVERVIEW APPENDIX E E ...
Page 660: ...F 12 C60 Breaker Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 670: ...H 8 C60 Breaker Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Page 672: ...H 10 C60 Breaker Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...
Page 682: ...x C60 Breaker Protection System GE Multilin INDEX ...