B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT DESCRIPTION
CHAPTER 2: PRODUCT DESCRIPTION
2
the system. Events can also be programmed (via FlexLogic
™
equations) to trigger oscillography data capture that can be
set to record the measured parameters before and after the event for viewing on a computer. These tools significantly
reduce troubleshooting time and simplify report generation in the event of a system fault.
Several options are available for communication. An RS232 port (USB port with the graphical front panel) can be used to
connect to a computer to program settings and monitor actual values. The rear RS485 port allows independent access by
operating and engineering staff. It can be connected to system computers with baud rates up to 115.2 kbps. All serial ports
use the Modbus RTU protocol. The IEC 60870-5-103 protocol is supported on the RS485 interface. Also only one of the DNP,
IEC 60870-5-103, and IEC 60870-5-104 protocols can be enabled at any time on the relay. When the IEC 60870-5-103
protocol is chosen, the RS485 port has a fixed even parity and the baud rate can be either 9.6 kbps or 19.2 kbps. The
100Base-FX or 100Base-TX Ethernet interface provides fast, reliable communications in noisy environments. The Ethernet
port supports IEC 61850, Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access
to the relay via any standard web browser (B30 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet
port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when
purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
Settings and actual values can be accessed from the front panel or EnerVista software.
The B30 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
Table 2-1: ANSI device numbers and functions supported
Device
number
Function
Device
number
Function
27P
Phase undervoltage
50/87
Unrestrained bus differential
49
Thermal overload protection
51G
Ground time overcurrent
50BF
Breaker failure
51N
Neutral time overcurrent
50DD
Disturbance detector
51P
Phase time overcurrent
50G
Ground instantaneous overcurrent
59N
Neutral overvoltage
50N
Neutral instantaneous overcurrent
59P
Phase overvoltage
50P
Phase instantaneous overcurrent
59X
Auxiliary overvoltage
50/74
CT trouble
67P
Phase directional overcurrent
50G
Ground instantaneous overcurrent
87B
Restrained bus differential
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...