Latched mode is intended for transient signals such as trip, and it conforms to ISA-18.1-1979 (R2004) standard type M 6.
Figure 4-41: Annunciator alarm sequence in Latched mode
In Acknowledgeable mode, both Off to On and On to Off state changes in the configured operand cause the background to
flash; the window must be acknowledged/reset to cancel flashing. This mode conforms to ISA-18.1-1979 (R2004) standard
type R-6.
Figure 4-42: Annunciator alarm sequence in Acknowledgeable mode
To acknowledge/reset all annunciator windows on a page:
1.
On the graphical front panel, press the
RESET
pushbutton with none of the annunciator windows selected. The
flashing stops.
To acknowledge/reset a specific annunciator window:
1.
On the graphical front panel, press the Up, Down, Left, and Right pushbuttons to select the window, so that is has a
yellow outline. Press the
RESET
or
ENTER
pushbutton. While a window is selected, if that window has activated since
the last restart, the date/time of the last activation of that window displays in the header.
Or in the software, access
Actual Values > Graphical Panel > Annunciator Panel
.
An alarm remains in an alarm state (for example, displays red) when the condition remains. That is, if you
acknowledged a flashing alarm but the alarm condition remains, the background color remains red.
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...