4-2
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
ENERVISTA SOFTWARE INTERFACE
CHAPTER 4: INTERFACES
4
•
Remote resources
•
Testing
Factory default values are supplied and can be restored after any changes.
The following communications settings are not transferred to the B30 with settings files:
Modbus Slave Address
Modbus TCP Port Number
RS485 COM2 Baud Rate
RS485 COM2 Parity
COM2 Minimum Response Time
COM2 Selection
RRTD Slave Address
RRTD Baud Rate
IP Address
IP Subnet Mask
IP Routing
When a settings file is loaded to a B30 that is in-service, the following sequence occurs:
1.
The B30 takes itself out of service.
2.
The B30 issues a UNIT NOT PROGRAMMED major self-test error.
3.
The B30 closes the critical fail contact.
The Maintenance chapter outlines how to use a settings file in the .urs format for backup and restore.
4.1.3 Event viewing
In online or offline mode, you can view and analyze data generated by triggered parameters as follows:
•
Event recorder
— The event recorder captures contextual data associated with the last 1024 events, listed
chronologically from most recent to oldest
•
Oscillography
— The oscillography waveform traces and digital states are used to provide a visual display of power
system and relay operation data captured during specific triggered events
Event records are viewable at software and device-specific levels. Access the former under
Admin > Event Log > View
.
Access the latter under
Actual Values > Records > Event Record
.
Event record entries for CyberSentry are explained in the next chapter. The following table outlines some software-level
entries.
Table 4-1: Event record descriptions
Event
Description
EnerVista UR Setup SESSION STARTED
The EnerVista software was launched
Language was changed.
The user changed the software language using the
View > Language
menu item
DEFAULT USERS CREATED
The user management window was launched using the
Admin > User Management
menu
item
: Successful upload of firmware
END
Firmware verified
Firmware uploaded
Firmware erased
START: Upload new firmware
The firmware on a device was upgraded
EnerVista UR Setup EVENT LOG CLEARED The event record was cleared. All event records were deleted using the
Admin > Event Log >
Clear
menu item.
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...