background image

1048520C • September 2006

Copyright © 2006, GE Security Inc.

Alliance Arming Station • AL-1111, AL-1116

Installation Instructions

Introduction

This is the GE 

Alliance Arming Station Installation Instructions

 

for models AL-1111 (four-line LCD) and AL-1116 (four-line 
LCD with Smart Card reader). These units are used with Alliance 
control panels to control security system alarm and access func-
tions. Features include:

• Beeper.
• Integrated tamper switch.
• Four-line liquid crystal display (LCD).
• Multiple text formats.
• Embedded Smart Card reader (AL-1116 only).
• Access and system status LEDs.
• One open collector output to drive a small relay (an external 

UL Listed power supply is required for UL installations).

• One input for an egress function.
• Plastic hinged cover.

The unit may be used up to 5,000 ft. (1.5 km) from the control 
panel or 4 door/elevator controller DGP.

Note:  

An external UL Listed power supply is required for UL 
installations.

Installation

To install the unit, do the following:
1.

The cover is hinged at the bottom. To open, grasp the cover 
at the sides or the top and pull gently. The cover will swing 
down on its pins (

Figure 1

). To remove the cover, gently pry 

one of the pins away from the body of the unit and pull.

Figure 1. Unit front

2.

The metal mounting plate at the back of the unit is held by a 
locking screw (

Figure 2

). To remove the mounting plate, 

loosen the screw by at least 0.3 in. (8 mm), slide the 
mounting plate down, and then pull the bottom of the 
mounting plate away from the body of the unit.

Figure 2. Unit back and mounting plate

3.

Attach the mounting plate to the mounting surface using the 
three screws provided.

4.

Set the RAS address using DIP switches 1 though 4 (see 

DIP switch settings

 on page 2).

5.

Set the system bus termination switch using DIP switch 5, if 
required.

6.

Wire the COMMS system bus cabling (see 

Wiring

 on 

page 2).

Note:  

All power should be turned off to the control panel before 
wiring the unit.

7.

Insert plastic cable entry blanking plugs (provided) into the 
back of the unit to blank any unused cable entry channels 
(

Figure 2

).

8.

Place the unit onto the mounting plate and move the unit 
down about 0.3 in. (8 mm) to lock in place.

9.

Tighten the locking screw at the base of the unit until firm. 
This will also ensure that the tamper switch (

Figure 2

) i

properly secured. Do not overtighten the screw.

Power

Fault

Access

Alarm

Status LEDs

LCD screen

Keypad

Area LEDs

Cover

Terminals

Cable

Tamper
  switch

Mounting
holes

Mounting
plate

Cable
entry

entry

Cable
entry

Locking screw

          DIP 
switches

Summary of Contents for AL-1111

Page 1: ...one of the pins away from the body of the unit and pull Figure 1 Unit front 2 The metal mounting plate at the back of the unit is held by a locking screw Figure 2 To remove the mounting plate loosen the screw by at least 0 3 in 8 mm slide the mounting plate down and then pull the bottom of the mounting plate away from the body of the unit Figure 2 Unit back and mounting plate 3 Attach the mounting...

Page 2: ...e RS 485 system bus You can connect the unit up to 5 000 ft 1 5 km from the control panel or 4 door elevator controller DGP We recommend you use a Beldon 8723 twisted pair shielded data cable The shield of any system bus cable must be connected to system ground at one end only This unit does not provide an Earth connection for this purpose If you daisy chain the system bus to the unit ensure that ...

Page 3: ...to arm Operating features The unit includes the following features Keyboard backlight and night light By default the keyboard backlight is on bright for approximately 4 15 minutes following a key press The night light by default is on dim To change these options see Menu options on page 4 LCD contrast To adjust the LCD contrast press and hold the Menu key Figure 1 on page 1 while you press the Up ...

Page 4: ...ter Press 0 Enter to exit the RAS main menu Submenus typically offer a choice between a default setting and alternative settings Navigate the submenus in the following manner Press Enter to accept the currently displayed setting and to return to the main menu Press Menu to scroll to an alternative setting Menu options The RAS menu provides numbered options Options 7 to 12 apply only to the AL 1116...

Page 5: ... or disable the use of reader configuration cards at the AL 1116 reader If you wish to prevent modification of the reader setup by configuration card you should disable this option 12 Last card Use this option to display the number of the last card badged at the AL 1116 reader The format shows the facility code and the ID number Offline mode If the unit has power available but loses communication ...

Page 6: ...to radio or tele vision reception which can be determined by turning the equip ment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet or a circuit different than that to which the receiver is connected...

Reviews: