3.18 DR-##
Data
Read-outs
Parameter group related to data readouts in the drive for
references, voltages, control, alarms, warnings, and status
words.
3.18.1 DR-0# General Status
Parameters to view the calculated references, the active
control word, and status word.
DR-00 Control Word
Range:
Function:
0
*
[0 - 65535] View the Control word sent from the frequency
converter via the serial communication port in
hex code.
DR-01 Reference [Unit]
Range:
Function:
0 ReferenceFeed-
backUnit
*
[-999999 - 999999
ReferenceFeed-
backUnit]
View the present
reference value applied
on impulse or analog
basis in the unit
resulting from the
configuration selected
in
H-40 Configuration
Mode
(Hz, Nm or RPM).
DR-02 Reference [%]
Range:
Function:
0 %
*
[-200 - 200
%]
View the total reference. The total
reference is the sum of digital, analog,
preset, bus, and freeze references, plus
catch-up and slow-down.
DR-03 Status Word
Range:
Function:
0
*
[0 - 65535] View the Status word sent from the frequency
converter via the serial communication port in
hex code.
DR-05 Main Actual Value [%]
Range:
Function:
0 %
*
[-100 - 100 %] View the two-byte word sent with the
Status word to the bus Master reporting
the Main Actual Value.
DR-09 Custom Readout
Range:
Function:
0 CustomRea-
doutUnit
*
[0 - 0 CustomRea-
doutUnit]
View the value of
custom readout from
to
3.18.2 DR-1# Motor Status
Parameters to view the motor status values.
DR-10 Power [kW]
Range:
Function:
0 kW
*
[0 -
10000 kW]
Displays motor power in kW. The value
shown is calculated on the basis of the actual
motor voltage and motor current. The value
is filtered, and therefore approx. 30 ms may
pass from when an input value changes to
when the data read-out values change. The
resolution of read-out value on fieldbus is in
10 W steps.
DR-11 Power [hp]
Range:
Function:
0 hp
*
[0 - 10000
hp]
View the motor power in HP. The value
shown is calculated on the basis of the
actual motor voltage and motor current. The
value is filtered, and therefore approximately
30 ms may pass from when an input value
changes to when the data read-out values
change.
DR-12 Motor Voltage
Range:
Function:
0 V
*
[0 - 6000 V] View the motor voltage, a calculated value
used for controlling the motor.
DR-13 Frequency
Range:
Function:
0 Hz
*
[0 - 6500 Hz] View the motor frequency, without
resonance dampening.
DR-14 Motor current
Range:
Function:
0 A
*
[0 - 10000
A]
View the motor current measured as a mean
value, I
RMS
. The value is filtered, and thus
approximately 30 ms may pass from when
an input value changes to when the data
read-out values change.
DR-15 Frequency [%]
Range:
Function:
0 %
*
[-100 -
100 %]
View a two-byte word reporting the actual
motor frequency (without resonance
dampening) as a percentage (scale 0000-4000
Hex) of
. Set
index 1 to send
it with the Status Word instead of the MAV.
Parameter Descriptions
AF-650 GP Programming Guide
DET-618C
113