Advent Commercial Fire System
Alarm Settings
Alarm settings specify how the panel behaves during cer-
tain alarm situations. Alarm settings are global.
Menu Output Text
49003
(Partitions-X10)
(Default = none) Use the following guidelines to “name” the X10
and non-X10 menu output numbers that appear in the “Lights/
Devices” user menus.
Use the item numbers that appear in Table B.2 on page 92
for characters and words listed there.
If a desired word does not appear in Table B.2, create it
using the characters (custom text).
Note
Only preprogrammed words from Table B.2 can be spo-
ken by the panel. Silence takes the place of any created
words when the panel voice speaks. However, created
words are displayed just like preprogrammed words.
When using words from Table B.2, spaces between them
appear automatically. When using characters from Table
B.2 to create words, you must reserve an item number for
a ‘space’ after the word.
Each character or word uses up one item number. For
example, a word from the list counts as one item number.
A created word (such as BOY’S) counts as six item num-
bers—4 letters, 1 apostrophe, and 1 space.
Only 8 item numbers are allowed for each output name, so
plan ahead before programming output text. You may
need to abbreviate words to avoid running out of item
numbers.
To Program Output Text:
1.
Once in program mode enter
49003
.
The display
shows
ENTER OUTPUT NUMBER OR PRESS * TO
CANCEL
.
2.
Enter the desired output number as follows:
Partition 1—1 thru 40
Partition 2—41 thru 80
Partition 3—81 thru 120
Partition 4—121 thru 160
Partition 5—161 thru 200
Partition 6—201 thru 240
Partition 7—241 thru 280
Partition 8—281 thru 320
Note
Entering an output number outside the range for a given
partition is indicated by an “Invalid” message.)
3.
Press
ƒ
. The display shows
TEXT FOR OUTPUT nn IS
current text
.
ENTER TEXT NUMBERS OR PRESS # TO
ACCEPT
.
4.
Enter the numbers of the desired characters or words. If
you make a mistake press
‚
to start over.
5.
Once all numbers have been entered, press
ƒ
to accept.
The display shows the new output text.
To Delete Output Text:
1.
Once in program mode enter
49003
.
The display
shows
ENTER OUTPUT NUMBER OR PRESS * TO
CANCEL
.
2.
Enter the desired output number and press
ƒ
. The display
shows
TEXT FOR OUTPUT nn IS current text
.
ENTER
TEXT NUMBERS OR PRESS # TO ACCEPT
.
3.
Enter
000
and press
ƒ
. The display shows
TEXT FOR
OUTPUT nn IS NO TEXT
.
Alarm Messages Played at High Volume
17079
(Alarms)
(Default = on) Choose whether or not you want alarm messages
(on voice siren)
always
played at high volume. If not, they will be
played at normal volume.
Note
Auxiliary/Medical alarm messages are never sounded at
high volume regardless of this setting.
To set Alarm Message Volume:
Once the item number has been entered, enter
1
for on (high
volume), or
0
for off (normal volume). Press
ƒ
to apply the new
setting.
Play Evacuation Messages During Fire Alarm
17083
(Alarms)
(Default = on) Choose whether or not fire alarm evacuation audio
messages are played during fire alarms. If off, evacuation
messages will not play during fire alarms.
To turn Play Evacuation Messages During Fire
Alarm On/Off:
Once the item number has been entered, enter
1
for on, or
0
for
off. Press
ƒ
to apply the new setting.
Evacuation Message Count
17104
(Alarms)
(Default = 4 messages) Set the number of evacuation messages
(0–4) to be played.
0 = No Messages
1 = English
2 = Spanish
3 = French
4 = Portuguese
Evacuation messages are automatically played until the siren
times out, the alarm is silenced, or the alarm is canceled. This
setting determines the number of evacuation messages played
starting with number 1 and up (then repeated). For example, if set
to 2, evacuation messages 1 and 2 will be played and repeated.
Note
In order for the panel to play evacuation messages during
fire alarms, the
Play Evacuation Messages During Fire
Alarm
setting (17083)
must be set to “on”.
To set Evacuation Message Count:
Once the item number has been entered, enter the evacuation
message count (0–4) and press
ƒ
.