Advent Commercial Fire System
Zone Attributes (Edit Zones)
47004
(Zones)
(Default = n/a) Use this item number to edit the following zone
attributes.
1—Critical Security Zone (Default = 0 [Off])
Enter 0 to turn attribute Off, 1 to turn attribute On. Critical
zones require special authority (partition master and full
authority codes) in order to be bypassed.
2—RF Supervisory Time (Default = A [4 hours])
Enter 0 for RF Supervisory Time A (17049), 1 for
Supervisory Time B (17050).
3—Zone Activity Threshold (Default = 0 [None])
Enter 0 for None, 1 for Threshold 1 (xx018), 2 for Thresh-
old 2 (xx019), 3 for Threshold 3 (xx020).
4—Hardwire Smoke Verify (Default = 0 [Off])
Enter 0 to turn attribute Off, 1 to turn attribute On. If on,
when a hardwire smoke detector is tripped, the panel will
remove power for 3 seconds to reset the smoke. If a sec-
ond trip occurs within 120 seconds, an alarm will sound
and a report will be sent to the central station.
5—Delayed Zone (Default = 0 Off)
Enter 0 to turn attribute Off, 1 to turn attribute On (see
17117).
6—Floor (Default = 0 [None])
Enter the floor number the zone resides on (1–90 above
ground, 91–99 below ground, 0 = None) (see item 17074
on page 46).
7—not supported
8—not supported
9—not supported
10—Warning message index (Default = 0 [None])
Enter the desired warning message (1–5). If learned into
zone type 70 it will play the desired warning message.
1 = Evacuation Message 1
2 = Evacuation Message 2
3 = Evacuation Message 3
4 = Evacuation Message 4
5 = Weather Warning Message
11—Zone Bypass Group (Default = 0 [None])
Enter the desired bypass group number (0–32). This will
allow users to directly bypass and unbypass groups of
zones.
To Edit Zone Attributes:
1.
Once in program mode enter
47004
.
The display
shows
ENTER ZONE NUMBER OR PRESS * TO CAN-
CEL
.
2.
Enter the desired zone number and press
ƒ
. The display
shows
ENTER ATTRIBUTE NUMBER OR PRESS * TO
CANCEL.
3.
Enter the attribute number from the list above and press
ƒ
. The display will show the current attribute setting. If
desired, change the attribute setting.
4.
Press
ƒ
to apply changes. To edit another attribute repeat
step 1.
Test Buddies
47005
(Zones)
(Default = n/a) Use this item number to test zone buddies.
To Test Buddies:
Once in program mode enter
47005
.
The display will show
BUDDY TEST MODE
. Once the test is complete the display will
list buddies (see List Buddies 47006).
List Buddies
47006
(Zones)
(Default = n/a) Use this item number to list information about
existing buddy zones. The system will list the buddy zone
number, ID, and latest buddy test results.
To List Buddies:
Once in program mode enter
47006
.
The display will list all
four buddies.
If the buddy doesn’t exists, the panel will display
BUDDY
n INVALID
.
If the buddy failed the latest test (47005), the panel will
display
BUDDY n FAILED
.
If the buddy passed the latest test, the signal strength will
be displayed.
The panel will scroll through and display information about each
buddy. To skip forward press
ƒ
. To exit press
‚
. Once the panel
lists all the buddies it will return to the program menu.
Zone Delay Time
17117
(Zones)
(Default = 10 seconds) Set the time delay (in seconds) between a
zone being tripped and the trip being processed by the panel. This
allows time for a zone to reset.
Note
This setting only applies to zones programmed as
delayed.
To set Zone Delay Time:
Enter the item number. Enter the delay time (1–250 seconds) and
press
ƒ
.
Smoke Loop Reset Time
17051
(Zones)
(Default = 3 seconds) Select the time (in seconds) for a zone to
reset.
To set Smoke Loop Reset Time:
Enter the item number. Enter the reset time (3-15 seconds) and
press
ƒ
.
Summary of Contents for Advent