Advent Commercial Fire System
About This Manual
This manual provides information for planning, installing,
programming, and testing an Advent Commercial security
or fire system. When necessary, this manual refers you to
other documentation included with compatible peripherals.
“Appendix A: System Configuration Worksheets” on
page 63 are included for you to record hardware layout and
software programming settings.
About the User Guide
The
User Guide
contains user worksheets that should be
filled out during the installation and programming of the
system.
Special Installation Requirements
Commercial Fire Panel
The commercial fire panel can be used as a fire warning
system and an intrusion alarm system. When using the com-
mercial fire panel as both a fire warning and intrusion alarm
system, follow the guidelines below:
All aspects of fire and burglary applications must occur in
separate partitions/areas.
All onboard panel inputs and outputs must be used only
for fire or burglary applications. Do not mix fire and bur-
glary applications.
Bus 1 and Bus 2 headers must be used only for fire or bur-
glary applications. Do not mix fire and burglary applica-
tions on inputs and outputs of any bus device.
Some installations may require configurations dictated by
city/state codes, insurance, or Underwriter’s Laboratories
(UL). See “
UL Listed Installations
” for various UL com-
ponent and configuration listings.
UL Listed Installations
This section describes the minimum requirements for differ-
ent UL Listed installations.
Basic System
Commercial Fire (60-562-03 or 60-562-06) Control Panel
SuperBus 2000 VFD (60-804-01) or LCD (60-803-01)
Alphanumeric Touchpad
24 VAC output, 100 VA Class I, 110VAC, 60 Hz (60-830)
or 24 VAC output, 100 VA Class II, 110VAC, 60 Hz (60-
823) Line Carrier AC Power Transformer
17.2 AH or 18.0 AH Backup Battery(s) (60-781)
Backup Battery Cable Assemblies (49-475 [red] and 49-
476 [black])
UL listed 4 ohm, 15W Speaker
2K ohm EOL Resistor(s) (49-467) or (49-454)
Police Station Connected Burglary Alarm Units and
Systems (UL 365)
The system Feature Numbers shall be set as follows in UL
365 listed systems:
Local Burglar Alarm Units and Systems (UL 609)
System Setup and Programming
The system Feature Numbers shall be set as follows in UL
609 listed systems:
Table 1. UL 365 Listed System Settings
Feature
No.
Feature
Required Setting
xx002
Siren Time Out
16 min. minimum
xx003
Standard Entry Delay
45 sec. maximum
xx004
Exit Delay
60 sec. maximum
yy003
Number of Attempts
5 min. 10 maximum
yy004
Communication Format
0 Contact ID
xx088
Report Partition/Area Events
to Central Station
1-On
xx092
Enable Auto Force Arming
0-Off
xx097
Exterior Arming Verification
0-Off
xx098
Audible Verification at Close
Report
1-On
xx102
One-Time Reset Enabled
0-Off
xx108
Enable Daily Reporting of
Partition Trouble
1-On
17034
Phone Test Interval
1 Day
17036
AC Stable Time
90 sec. maximum
17041
Hours to Delay Before
Reporting AC Failure
8 hours (or less)
17049
RF Supervisory Time A
4 hours
17069
No Phone Line Attached
0-Off
17072
Enable RF Jam Detect
1-On
17073
Battery Test Interval
1=4 hours
17076
Commercial or Residential
Installation
1-Commercial
17078
Detect Receiver Failure
1-On
17079
Alarm Messages Played at
High Volume
1-On (High)
17096
Report System Events
1-On
47004
Zone Attributes (edit zones)
N/A
xx = Two digit partition number.
yy = Two digit non-pager phone number.
Table 2. UL 609 Listed System Settings
Feature
No.
Feature
Required Setting
xx002
Siren Time Out
16 min. minimum
yy004
Communication Format
0 Contact ID
xx088
Report Partition/Area Events
to Central Station
1-On
xx092
Enable Auto Force Arming
0-Off
xx097
Exterior Arming Verification
0-Off