Advent Commercial Fire System
Generate Alarm for Suspicion Trips
xx078
(Partitions-Alarms)
(Default = on) This setting allows you to enable the panel to
generate a suspicion trip alarm. If on, and suspicion zones are
tripped, an alarm will be generated after the
Delay Between
Suspicion Zone Trip and Alarm Generated
(xx015) expires. If off,
the tripping of suspicion zones will not generate an alarm.
To turn Generate Alarm for Suspicion Trips On/
Off:
Once the item number has been entered, enter
1
for on or
0
for
off. Press
ƒ
to apply the new setting.
Delay Between Suspicion Zone Trip and Alarm
Generated
xx015
(Partitions-Alarms)
(Default = 05 Minutes) Select the length of time in minutes in
which an alarm can be avoided after a suspicion zone is tripped.
This allows the user time to prevent a false alarm from being
generated.
Programming the Delay Between Suspicion Trip
and Alarm Generated:
Once the item number has been entered, enter the number of
minutes (1–15) you wish the panel to wait before going into
alarm. Press
ƒ
to apply the new setting.
Note
If the
Generate Alarm for Suspicion Trips
setting (xx078)
is set to off, this setting will have no effect.
First Trip Local Second Trip Event
xx080
(Partitions-Alarms)
(Default = off) If on, the first zone trip in a two trip zone type (18
or 77) causes a local police alarm. A second zone trip from a
different zone, occurring within four minutes of the first zone trip,
generates a report. Zones must reside in the same partition/area. If
off, the first zone trip starts a timer and the second zone trip
causes the alarm and report.
To turn this setting On/Off:
Once the item number has been entered, enter
1
for on or
0
for
off. Press
ƒ
to apply the new setting.
Disable Siren
xx081
(Partitions-Alarms)
(Default = on) Select whether or not you want to disable siren
time-out for fire alarms. If disabled, a siren will continue to sound
until the system is disarmed.
Note
This option is not available in UL-864 version.
To turn this setting On/Off:
Once the item number has been entered, enter
1
for on or
0
for
off. Press
ƒ
to apply the new setting.
Agent Release Zone 1
Agent Release Zone 2
1: xx122, 2: xx123
(Partitions-Alarms)
(Default = Off) This setting allows you to specify which zones,
when tripped, cause an output to release an extinguishing agent.
Note
All aspects of an agent release should occur in the same
partition. All zones, outputs, and devices relating to an
agent release should physically reside and be pro-
grammed into the same partition.
Select the zone number that, when tripped, causes an agent
release.
Note
This option is not available in UL-864 version.
To turn this setting On/Off:
Once the item number has been entered, enter
1
for on or
0
for
off. Press
ƒ
to apply the new setting.
Manual Agent Release Delays
xx125
(Partitions-Alarms)
(Default = 0) This setting allows you to specify delay times (0-30
seconds) before an agent is released after an alarm has been
triggered. Manual agent release cannot be aborted.
Note
This option is not available in UL-864 version.
To turn this setting On/Off:
Once the item number has been entered, enter
1
for on or
0
for
off. Press
ƒ
to apply the new setting.
Automatic Agent Release Delays
xx124
(Partitions-Alarms)
(Default = 30) This setting allows you to set the automatic agent
release delay time (0-60 seconds). Automatic agent release may
be aborted during the delay.
Note
This option is not available in UL-864 version.
To turn this setting On/Off:
Once the item number has been entered, enter
1
for on or
0
for
off. Press
ƒ
to apply the new setting.