background image

DEH40151 

DEH40151   Rev.No.02 

1

g        

A-Series 

®

 II Panelboards 

AD/AE/AQ Type P & N Power Panel 
SF Three-Phase Circuit Breaker Kits 

Introduction 

 
These instructions describe the installation of SF three-phase circuit breaker kit into an 
A-Series

®

 II panelboard. These kits are for use in panelboards ordered with Un-Specified 

Space. 
The catalog number for three-pole SF breaker kit is ASPP6SF3S 

Parts List for ASPP6SF3S 

Table 1. 

ITEM # 

DESCRIPTION 

PART # 

QTY 

BRANCH BASE FOR B PHASE 

139C5702BSFG1 

BRANCH BASE FOR A PHASE 

139C5702ASFG1 

BRANCH BASE FOR C PHASE 

139C5702CSFG1 

4 (SPOOL) 

315A7036P20 

5 (SCREW-SPOOL) 

315A7037P1 

6 (WASHER-SPOOL) 

75A105503P111  3 

7 (SCREW-BUS) 

315A7034P6 

8 3P 

BRACKET 

139C5500P84 

SCREW, BKT TO RAIL 

N37P16060B6 

10 CUP 

WASHER, 

N405P40B6 

11 

FILLER PLATE, SF/TFJ 

139C5503P90 

12 

SCREWS , #10-32 X 3/8 

N722P16006B6 

 

Installation 
 
WARNING

Before attempting to install one of these kits, remove all power from the 

panelboard.

 

 
Use the following procedure to install a SF circuit breaker kit. Call-out numbers in the 
illustrations and numbers in brackets in the text refer to the Item Numbers in Table 1. 
Installation of a three-pole kit is illustrated in Figure 1 or Figure 2. 
 

1.  Remove the interior assembly from its packaging and verify that all parts are 

present, as given in the parts list. 

2.  Remove the 8 screws (600A and 800A panels) securing the dead front to 

panelboard interior. Lift off the dead front and place it and the screws aside. 

3.  Remove the circuit breaker kit from its packaging and verify that all parts are 

present, as given in the packing list. 

4.  Refer fig. no.1 to mount the breaker on left side of interior. Place branch base for 

A phase [2] adjacent to cross bar [13] as shown in fig.1 and insert the screw [7] 
through slot provided for A phase to clamp it with main busbar. Similarly mount 

Summary of Contents for A-Series II Panelboard

Page 1: ...WS 10 32 X 3 8 N722P16006B6 4 Installation WARNING Before attempting to install one of these kits remove all power from the panelboard Use the following procedure to install a SF circuit breaker kit Call out numbers in the illustrations and numbers in brackets in the text refer to the Item Numbers in Table 1 Installation of a three pole kit is illustrated in Figure 1 or Figure 2 1 Remove the inter...

Page 2: ...erior catalog number ASPP6SF3S into an A Series II Panelboards 5 Refer fig no 2 to mount the breaker on left side of interior Place branch base for A phase 2 adjacent to cross bar 13 as shown in fig 1 and insert the screw 7 through slot provided for A phase to clamp it with main busbar Similarly mount B phase 1 branch busbar to B phase main busbar but adjacent to A phase branch base and C phase 3 ...

Page 3: ... to the underside of the breaker terminal with the screws 5 Take care to assemble the screws to the spools as shown in Figure 1 or Figure 2 with the tapped end of the spool toward the breaker terminal 8 Place the breaker over branch base 1 2 and 3 align the spool 4 with protruded opening in branch bases and tighten the three 28 X 1 3 8 screws 5 installed in step 7 to 60 in lb Maximum 9 Insert two ...

Page 4: ...ated in Figure 4 Fasten filler plate to the dead front with four 10 32 x 3 8 screws 12 tightened to 27 36 in lb 12 To install branch breaker kit ASPP6SF3S on right side of interior flip filler plate 11 and place it over the dead front so that the four same size holes line up with the threaded holes of the dead front as similar to step 11 Fasten filler plate to the dead front with four 10 32 x 3 8 ...

Page 5: ...d after SG as shown in Figure 5 then gap between the breakers dim A has to be followed as mentioned in Table 2 Replace the subsequent blank filler of dead front with SF filler plate given in kit ASPP6SF3S using steps 10 to 13 15 If SF breaker has to be installed immediately after crossbar as shown in Figure 6 then gap between the breaker and crossbar has to be 0 061inch ...

Page 6: ...DEH40151 DEH40151 Rev No 02 6 Figure 5 Distance between breakers Table 2 Distance between breakers Gap with Breaker A in SG 0 582 ...

Page 7: ...riations in equipment nor do they provide for every possible contingency that may be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be referred to the GE Company ...