4–354
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
TESTING
CHAPTER 4: SETPOINTS
To configure the pickup setpoint for a total arcing current of 5000kA
2
/cycle, the per-unit
pickup value can be calculated as follows:
Pickup = 5000kA
2
*cycle/2000 kA
2
*cycle = 2.500 pu
Testing
Figure 4-141: Testing Display Hierarchy
Path:
Setpoints > Testing
•
Simulation
•
Test LEDs
•
Contact Inputs
•
Output Relays
The 8 Series can simulate current and voltage inputs when the Simulation feature is
enabled. Other test operations are also possible such as the LED lamp test of each color,
contact input states and testing of output relays.
Pre-Fault
Setpoints
Device
System
Inputs
Outputs
Protection
Monitoring
Control
FlexLogic
Level 1
Level 2
Level 3
Level 4
Setup
Testing
Simulation
Test LEDs
Contact Inputs
Output Relays
Fault
Post-Fault
Summary of Contents for 845
Page 10: ...VIII 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 219: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 91 ...
Page 221: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 93 ...
Page 222: ...4 94 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 223: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 95 ...
Page 224: ...4 96 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 225: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 97 ...
Page 226: ...4 98 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 227: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 99 ...
Page 396: ...4 268 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL MONITORING CHAPTER 4 SETPOINTS ...
Page 526: ...6 22 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...