845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL
CHAPTER 4: SETPOINTS
Arc Flash Protection
The Arc Flash Protection module supports fast and secure protection against an arc flash
event for a safe working environment.
Arc Flash protection utilizes a total of four light detection fiber sensors and dedicated high-
speed instantaneous overcurrent element with secure Finite Response Filtering. Light from
the light sensor AND logic with high-speed overcurrent ensures fast and secure operation.
Further enhancement includes continuous monitoring of individual light sensors with self-
test trouble indication. Four Arc Flash elements with self-test from the individual light
sensors can be used to design flexible Arc Flash protection schemes for different
configurations depending upon the physical locations of the sensors. Each individual
element can also provide a higher level of redundancy/reliability of the system.
In case any issues with the sensors are detected (i.e. failure of a self-test), the
corresponding light sensor trouble operands (i.e. “Light Sensor # Trouble” and “Light Sensor
Trouble”) are asserted. Very fast detection of the Arc flash light event is also possible using
Light as the only detection parameter for alarm purposes. In addition, a user can design
customized logic using individual “AF1 Light # PKP” and “Arc Flash 1 S# OP” operands from
different light sensors in the FlexLogic engine.
Path
:
Setpoints > Control > Arc Flash > Arc Flash 1
FUNCTION
Range: Disabled, Trip, Alarm, Latched Alarm, Configurable
Default: Disabled
The selection of Trip, Alarm, Latched Alarm or Configurable setting enables the HS
Phase/Ground IOC function.
HS PHASE PKP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 2.000 x CT
HS GROUND PKP
Range: 0.050 to 30.000 x CT in steps of 0.001 x CT
Default: 1.000 x CT
NOTE
NOTE:
The value of HS Gnd PICKUP can be set to a very high value, when only the HS Phs element
needs to be applied for Arc Flash detection.
NOTE
NOTE:
The HS Ground PKP setting is not available if the order code is selected to have just one
sensitive ground current input on the J1-Bank (4-0B in the order code).
LIGHT SENSOR 1(4)
Range: Disabled, Enabled
Default: Disabled
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
OUTPUT RELAY X
For details see
EVENTS
Range: Disabled, Enabled
Default: Enabled
This setting enables or disables the events of the Arc Flash function.
Summary of Contents for 845
Page 10: ...VIII 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 219: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 91 ...
Page 221: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 93 ...
Page 222: ...4 94 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 223: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 95 ...
Page 224: ...4 96 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 225: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 97 ...
Page 226: ...4 98 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL SYSTEM CHAPTER 4 SETPOINTS ...
Page 227: ...CHAPTER 4 SETPOINTS SYSTEM 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL 4 99 ...
Page 396: ...4 268 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL MONITORING CHAPTER 4 SETPOINTS ...
Page 526: ...6 22 845 TRANSFORMER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...