1-8
735/737 Feeder Protection Relay
GE Power Management
1.3 SPECIFICATIONS
1 INTRODUCTION
1
1.3.5 MISCELLANEOUS
INDICATORS
Phase time overcurrent trip A,B,C (latched)
Phase instantaneous overcurrent trip A,B,C (latched)
Ground fault time overcurrent trip (latched)
Ground fault instantaneous overcurrent trip (latched)
Relay in service
Service required
Phase pickup
Ground pickup
Current level LED bargraph:10-100%
ENVIRONMENT
Operating temperature range: –40°C to +70°C
TYPE TESTING
Insulation Resistance:
per IEC 255-5 (500 V DC, 2000 M
Ω
)
Dielectric Strength:
per IEC 255-5 and ANSI/IEEE C37.90 (2 kV at 60 Hz for 1 minute)
Impulse Voltage
per IEC 255-5 (5 kV)
Surge Immunity:
per EN 61000-4-5 (common mode 4 kV, differential modes 2 kV)
Oscillatory Surge Withstand:per ANSI/IEEE C37.90.1, per Ontario Hydro A-28M-82
Voltage Dips
per IEC 61000-4-11 (0%, 40%, 70%)
Electrostatic Discharge: per IEC 255-22-2 (4/4 kV)
Damp Heat (Humidity Cyclic):per IEC 68-2-30 (6 days)
Make and Carry for relays:per IEEE C37.90 (30 A)
Current Withstand:
per ANSI/IEEE C37.90 (40
×
rated 1 A for 2 seconds;
60
×
rated 5 A for 1 second
)
RFI Radiated Immunity: per IEC 255-22-3 (160 MHz, 460 MHz), per EN 61000-4-3 (10 V/m)
RFI Conducted Immunity:per EN-61000-4-6 (10 V)
Temperature Cycle:
–40°C, +60°C (per GE internal procedures)
Mechanical Stress:
2 g (per GE internal procedures)
Current Calibration:
per GE internal procedures
10 A DC continuous relay current carry at 80°C per GE internal procedure
It is recommended that the 735/737 relays be powered up at least once per year to avoid deterioration of
electrolytic capacitors in the power supply.
NOTE
Summary of Contents for 735
Page 10: ......
Page 12: ......
Page 16: ...iv 735 737 Feeder Protection Relay GE Power Management TABLE OF CONTENTS ...
Page 98: ...6 8 735 737 Feeder Protection Relay GE Power Management 6 2 TEST RECORDS 6 TESTING 6 ...
Page 100: ...7 2 735 737 Feeder Protection Relay GE Power Management 7 1 SETTINGS TABLE 7 COMMISSIONING 7 ...
Page 108: ...iv 735 737 Feeder Protection Relay GE Power Management INDEX ...
Page 109: ...GE Power Management 735 737 Feeder Protection Relay NOTES ...