Product Summary

The siren combines speaker and piezo technology 
that produces a high-volume, low-current siren. A 
built-in tamper switch detects cover and/or siren 
removal. Mounting hardware and a cover screw are 
included.

Installation

Installation involves mounting, wiring, and testing.

Installation Guidelines

Mount siren where occupants can hear it. More 
than one siren may be required to cover all areas.

Make sure wire run from control panel to siren has 
correct number of conductors to provide for 
desired functions. For example, to use all siren 
functions (Steady, Warble, and Tamper), wire run 
must have five conductors.

For control panels with only one siren output, use 
siren terminal #1 (Steady).

When connecting siren Tamper to control panel 
zone input, install correct end-of-line (EOL) resis-
tor (included with control panel) at siren terminals.

Figure 1 shows siren with cover removed.

Figure 1.  Siren Components and Mounting Holes

Mounting

1. Select location for siren.

2. Run appropriate conductor wire from control panel 

to siren location.

3. Remove cover from siren.

4. Hold siren on wall at mounting location and mark 

desired mounting holes. If using wall tamper fea-
ture, be sure to mark wall tamper mounting hole.

5. Install plastic anchors (included) where studs are 

not present.

6. Insert wire through wire feed hole on siren.

7. Secure siren to wall with screws (included) at 

marked locations.

Wiring

1. Connect positive (+) siren outputs from control 

panel to siren terminals #1 (Steady) and #2 (War-
ble). For control panels with only one siren output, 
use #1 (Steady) terminal.

2. Connect control panel ground (-) to GND siren ter-

minal.

3. Connect wiring from control panel zone input to 

siren tamper terminals marked SW. Be sure to con-
nect EOL resistor in series with one of the termi-
nals.

4. Place cover on siren and secure on bottom using 

small flat head cover screw (included).

Testing

Caution!

Contact central monitoring station before testing the siren. 
Testing requires causing alarms to verify correct siren oper-
ation.

1. Contact central monitoring station and inform 

them you are testing the system.

2. Activate intrusion and fire alarms to verify siren 

operation.

3. Arm system and remove siren cover to verify 

tamper circuit works.

4. Replace siren cover.

5. Contact central monitoring station when you are 

finished testing.

Mounting Holes

Mounting Holes

Wall
Tamper
Mounting
Hole

Cover
Tamper

SW SW GND #2 #1

Wire
Feed
Hole

+DUGZLUH,QWHULRU6LUHQ

Document No. 466-2115  Rev. A

January 2004