5.7.10 DIRECT INPUTS AND OUTPUTS
a) DIRECT INPUTS
PATH: SETTINGS
INPUTS/OUTPUTS
DIRECT INPUTS
DIRECT INPUT 1(32)
These settings specify how the direct input information is processed. The
DIRECT INPUT 1 NAME
setting allows the user to
assign a descriptive name to the direct input. The
DIRECT INPUT 1 DEVICE ID
represents the source of direct input 1. The
specified direct input is driven by the device identified here.
The
DIRECT INPUT 1 BIT NUMBER
is the bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
identified as
DIRECT INPUT 1 BIT NUMBER
. This corresponds to the direct output number of the sending device.
The
DIRECT INPUT 1 DEFAULT STATE
represents the state of the direct input when the associated direct device is offline. The
following choices are available:
•
Setting
DIRECT INPUT 1 DEFAULT STATE
to “On” value defaults the input to Logic 1.
•
Setting
DIRECT INPUT 1 DEFAULT STATE
to “Off” value defaults the input to Logic 0.
•
Setting
DIRECT INPUT 1 DEFAULT STATE
to “Latest/On” freezes the input in case of lost communications. If the latest
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 1. When communication resumes, the input becomes fully operational.
•
Setting
DIRECT INPUT 1 DEFAULT STATE
to “Latest/Off” freezes the input in case of lost communications. If the latest
state is not known, such as after relay power-up but before the first communication exchange, the input will default to
Logic 0. When communication resumes, the input becomes fully operational.
b) DIRECT OUTPUTS
PATH: SETTINGS
INPUTS/OUTPUTS
DIRECT OUTPUTS
DIRECT OUTPUT 1(32)
The
DIRECT OUT 1 NAME
setting allows the user to assign a descriptive name to the direct output. The
DIR OUT 1 OPERAND
is
the FlexLogic operand that determines the state of this direct output.
c) APPLICATION EXAMPLES
The examples introduced in the earlier
Direct Inputs and Outputs
section (part of the
Product Setup
section) are continued
below to illustrate usage of the direct inputs and outputs.
DIRECT INPUT 1
DIRECT INPUT 1
NAME: Dir Ip 1
Range: up to 12 alphanumeric characters
MESSAGE
DIRECT INPUT 1
DEVICE ID: 1
Range: 1 to 16
MESSAGE
DIRECT INPUT 1
BIT NUMBER: 1
Range: 1 to 32
MESSAGE
DIRECT INPUT 1
DEFAULT STATE: Off
Range: On, Off, Latest/On, Latest/Off
MESSAGE
DIRECT INPUT 1
EVENTS: Disabled
Range: Enabled, Disabled
DIRECT OUTPUT 1
DIRECT OUT 1 NAME:
Dir Out 1
Range: up to 12 alphanumeric characters
MESSAGE
DIRECT OUT 1 OPERAND:
Off
Range: FlexLogic operand
MESSAGE
DIRECT OUTPUT 1
EVENTS: Disabled
Range: Enabled, Disabled
Summary of Contents for L60
Page 10: ...x L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 57: ...GE Multilin L60 Line Phase Comparison System 2 27 2 PRODUCT DESCRIPTION 2 3 SPECIFICATIONS 2 ...
Page 58: ...2 28 L60 Line Phase Comparison System GE Multilin 2 3 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 482: ...6 26 L60 Line Phase Comparison System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 554: ...10 8 L60 Line Phase Comparison System GE Multilin 10 2 BATTERIES 10 MAINTENANCE 10 ...
Page 674: ...B 110 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 704: ...C 30 L60 Line Phase Comparison System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Page 720: ...E 10 L60 Line Phase Comparison System GE Multilin E 1 PROTOCOL APPENDIX E E ...
Page 732: ...F 12 L60 Line Phase Comparison System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Page 742: ...H 8 L60 Line Phase Comparison System GE Multilin H 3 WARRANTY APPENDIX H H ...