B-32
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
7B81
User Programmable Pushbutton 1 Events
0 to 1
---
1
F102
0 (Disabled)
7B82
User Programmable Pushbutton 1 LED Operand
0 to 65535
---
1
F300
0
7B83
User Programmable Pushbutton 1 Autoreset Delay
0 to 600
s
0.05
F001
0
7B84
User Programmable Pushbutton 1 Autoreset Function
0 to 1
---
1
F102
0 (Disabled)
7B85
User Programmable Pushbutton 1 Local Lock
0 to 65535
---
1
F300
0
7B86
User Programmable Pushbutton 1 Message Priority
0 to 2
---
1
F220
0 (Disabled)
7B87
User Programmable Pushbutton 1 Remote Lock
0 to 65535
---
1
F300
0
7B88
User Programmable Pushbutton 1 Reset
0 to 65535
---
1
F300
0
7B89
User Programmable Pushbutton 1 Set
0 to 65535
---
1
F300
0
7B8A
User Programmable Pushbutton 1 Hold
0 to 10
s
0.1
F001
1
7B8B
...Repeated for User Programmable Pushbutton 2
7BB6
...Repeated for User Programmable Pushbutton 3
7BE1
...Repeated for User Programmable Pushbutton 4
7C0C
...Repeated for User Programmable Pushbutton 5
7C37
...Repeated for User Programmable Pushbutton 6
7C62
...Repeated for User Programmable Pushbutton 7
7C8D
...Repeated for User Programmable Pushbutton 8
7CB8
...Repeated for User Programmable Pushbutton 9
7CE3
...Repeated for User Programmable Pushbutton 10
7D0E
...Repeated for User Programmable Pushbutton 11
7D39
...Repeated for User Programmable Pushbutton 12
7D64
...Repeated for User Programmable Pushbutton 13
7D8F
...Repeated for User Programmable Pushbutton 14
7DBA
...Repeated for User Programmable Pushbutton 15
7DE5
...Repeated for User Programmable Pushbutton 16
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00
Neutral Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F01
Neutral Overvoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F02
Neutral Overvoltage 1 Pickup
0 to 3.00
pu
0.001
F001
300
7F03
Neutral Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7F04
Neutral Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7F05
Neutral Overvoltage 1 Block
0 to 65535
---
1
F300
0
7F06
Neutral Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F07
Neutral Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F08
Neutral Overvoltage 1 Curves
0 to 3
---
1
F116
0 (Definite Time)
7F09
Reserved (8 items)
0 to 65535
---
1
F001
0
7F10
...Repeated for Neutral Overvoltage 2
7F20
...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7F30
Auxiliary Overvoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F31
Auxiliary Overvoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F32
Auxiliary Overvoltage 1 Pickup
0 to 3
pu
0.001
F001
300
7F33
Auxiliary Overvoltage 1 Pickup Delay
0 to 600
s
0.01
F001
100
7F34
Auxiliary Overvoltage 1 Reset Delay
0 to 600
s
0.01
F001
100
7F35
Auxiliary Overvoltage 1 Block
0 to 65535
---
1
F300
0
7F36
Auxiliary Overvoltage 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7F37
Auxiliary Overvoltage 1 Events
0 to 1
---
1
F102
0 (Disabled)
7F38
Reserved (8 items)
0 to 65535
---
1
F001
0
7F40
...Repeated for Auxiliary Overvoltage 2
7F50
...Repeated for Auxiliary Overvoltage 3
Auxiliary Undervoltage (Read/Write Grouped Setting) (3 modules)
7F60
Auxiliary Undervoltage 1 Function
0 to 1
---
1
F102
0 (Disabled)
7F61
Auxiliary Undervoltage 1 Signal Source
0 to 5
---
1
F167
0 (SRC 1)
7F62
Auxiliary Undervoltage 1 Pickup
0 to 3
pu
0.001
F001
700
Table B–9: MODBUS MEMORY MAP (Sheet 25 of 50)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...