GE Multilin
C60 Breaker Protection System
5-159
5 SETTINGS
5.7 CONTROL ELEMENTS
5
The autoreclose scheme is intended for use on transmission lines with circuit breakers operated in both the single pole and
three pole modes, in one or two breaker arrangements. The autoreclose scheme provides four programs with different
operating cycles, depending on the fault type. Each of the four programs can be set to trigger up to four reclosing attempts.
The second, third, and fourth attempts always perform three-pole reclosing and have independent dead time delays.
When used in two breaker applications, the reclosing sequence is selectable. The reclose signal can be sent to one
selected breaker only, to both breakers simultaneously or to both breakers in sequence (one breaker first and then, after a
delay to check that the reclose was successful, to the second breaker). When reclosing in sequence, the first breaker
should reclose with either the single-pole or three-pole dead time according to the fault type and reclose mode; the second
breaker should follow the successful reclosure of the first breaker. When reclosing simultaneously, for the first shot both
breakers should reclose with either the single-pole or three-pole dead time, according to the fault type and the reclose
mode.
The signal used to initiate the autoreclose scheme is the trip output from protection. This signal can be single pole tripping
for single phase faults and three phase tripping for multi-phase faults. The autoreclose scheme has five operating states.
MESSAGE
AR RESET TIME:
60.00 s
Range: 0 to 655.35 s in steps of 0.01
MESSAGE
AR BKR CLOSED:
Off
Range: FlexLogic™ operand
MESSAGE
AR BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
AR PAUSE:
Off
Range: FlexLogic™ operand
MESSAGE
AR INCOMPLETE SEQ
TIME: 5.00 s
Range: 0 to 655.35 s in steps of 0.01
MESSAGE
AR BLOCK BKR2:
Off
Range: FlexLogic™ operand
MESSAGE
AR CLOSE TIME BKR2:
0.10 s
Range: 0.00 to 655.35 s in steps of 0.01
MESSAGE
AR TRANSFER 1 TO 2:
No
Range: Yes, No
MESSAGE
AR TRANSFER 2 TO 1:
No
Range: Yes, No
MESSAGE
AR BKR1 FAIL OPTION:
Continue
Range: Continue, Lockout
MESSAGE
AR BKR2 FAIL OPTION:
Continue
Range: Continue, Lockout
MESSAGE
AR 1-P DEAD TIME:
1.00 s
Range: 0 to 655.35 s in steps of 0.01
MESSAGE
AR BKR SEQUENCE:
1-2
Range: 1, 2, 1&2, 1–2, 2–1
MESSAGE
AR TRANSFER TIME:
4.00 s
Range: 0 to 655.35 s in steps of 0.01
MESSAGE
AR BUS FLT INIT:
Off
Range: FlexLogic™ operand
MESSAGE
AR EVENT:
Disabled
Range: Enabled, Disabled
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...