GE Multilin
C60 Breaker Protection System
5-125
5 SETTINGS
5.6 GROUPED ELEMENTS
5
c) PHASE TIME OVERCURRENT
(ANSI 51P)
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
Ö
PHASE CURRENT
Ö
PHASE TOC1(6)
The phase time overcurrent element can provide a desired time-delay operating characteristic versus the applied current or
be used as a simple definite time element. The phase current input quantities may be programmed as fundamental phasor
magnitude or total waveform RMS magnitude as required by the application.
Two methods of resetting operation are available: “Timed” and “Instantaneous” (refer to the Inverse
Time overcurrent
curves characteristic
sub-section earlier for details on curve setup, trip times, and reset operation). When the element is
blocked, the time accumulator will reset according to the reset characteristic. For example, if the element reset characteris-
tic is set to “Instantaneous” and the element is blocked, the time accumulator will be cleared immediately.
The
PHASE TOC1 PICKUP
setting can be dynamically reduced by a voltage restraint feature (when enabled). This is accom-
plished via the multipliers (Mvr) corresponding to the phase-phase voltages of the voltage restraint characteristic curve (see
the figure below); the pickup level is calculated as ‘Mvr’ times the
PHASE TOC1 PICKUP
setting. If the voltage restraint feature
is disabled, the pickup level always remains at the setting value.
PHASE TOC1
PHASE TOC1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
PHASE TOC1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
PHASE TOC1
INPUT: Phasor
Range: Phasor, RMS
MESSAGE
PHASE TOC1
PICKUP: 1.000
pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PHASE TOC1
CURVE: IEEE Mod Inv
Range: See Overcurrent Curve Types table
MESSAGE
PHASE TOC1
TD MULTIPLIER: 1.00
Range: 0.00 to 600.00 in steps of 0.01
MESSAGE
PHASE TOC1
RESET: Instantaneous
Range: Instantaneous, Timed
MESSAGE
PHASE TOC1 VOLTAGE
RESTRAINT: Disabled
Range: Disabled, Enabled
MESSAGE
PHASE TOC1 BLOCK A:
Off
Range: FlexLogic™ operand
MESSAGE
PHASE TOC1 BLOCK B:
Off
Range: FlexLogic™ operand
MESSAGE
PHASE TOC1 BLOCK C:
Off
Range: FlexLogic™ operand
MESSAGE
PHASE TOC1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
PHASE TOC1
EVENTS: Disabled
Range: Disabled, Enabled
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...