4-24
C60 Breaker Protection System
GE Multilin
4.3 FACEPLATE INTERFACE
4 HUMAN INTERFACES
4
c) FACEPLATE (USER KEY) CONTROL
After the 30 minute interval during which command functions are permitted after a correct command password, the user
cannot open or close a breaker via the keypad. The following discussions begin from the not-permitted state.
d) CONTROL OF TWO BREAKERS
For the following example setup, the
(Name)
field represents the user-programmed variable name.
For this application (setup shown below), the relay is connected and programmed for both breaker 1 and breaker 2. The
USER 1 key performs the selection of which breaker is to be operated by the USER 2 and USER 3 keys. The USER 2 key
is used to manually close the breaker and the USER 3 key is used to manually open the breaker.
e) CONTROL OF ONE BREAKER
For this application the relay is connected and programmed for breaker 1 only. Operation for this application is identical to
that described above for two breakers.
4.3.7 MENUS
a) NAVIGATION
Press the MENU key to select the desired header display page (top-level menu). The header title appears momentarily fol-
lowed by a header display page menu item. Each press of the MENU key advances through the following main heading
pages:
•
Actual values.
•
Settings.
•
Commands.
•
Targets.
•
User displays (when enabled).
ENTER COMMAND
PASSWORD
This message appears when the USER 1, USER 2, or USER 3 key is pressed and a
COMMAND PASSWORD
is required; i.e. if
COMMAND PASSWORD
is enabled and no com-
mands have been issued within the last 30 minutes.
Press USER 1
To Select Breaker
This message appears if the correct password is entered or if none is required. This mes-
sage will be maintained for 30 seconds or until the USER 1 key is pressed again.
BKR1-(Name) SELECTED
USER 2=CLS/USER 3=OP
This message is displayed after the USER 1 key is pressed for the second time. Three
possible actions can be performed from this state within 30 seconds as per items
(1)
,
(2)
and
(3)
below:
(1)
USER 2 OFF/ON
To Close BKR1-(Name)
If the USER 2 key is pressed, this message appears for 20 seconds. If the USER 2 key is
pressed again within that time, a signal is created that can be programmed to operate an
output relay to close breaker 1.
(2)
USER 3 OFF/ON
To Open BKR1-(Name)
If the USER 3 key is pressed, this message appears for 20 seconds. If the USER 3 key is
pressed again within that time, a signal is created that can be programmed to operate an
output relay to open breaker 1.
(3)
BKR2-(Name) SELECTED
USER 2=CLS/USER 3=OP
If the USER 1 key is pressed at this step, this message appears showing that a different
breaker is selected. Three possible actions can be performed from this state as per
(1)
,
(2)
and
(3)
. Repeatedly pressing the USER 1 key alternates between available breakers.
Pressing keys other than USER 1, 2 or 3 at any time aborts the breaker control function.
Summary of Contents for C60
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX ...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...