GE Multilin
C60 Breaker Protection System
2-17
2 PRODUCT DESCRIPTION
2.2 SPECIFICATIONS
2
2.2.11 TYPE TESTS
Electrical fast transient: ANSI/IEEE C37.90.1 *
IEC 61000-4-4
IEC 60255-22-4
Oscillatory transient:
ANSI/IEEE C37.90.1 *
IEC 61000-4-12
Insulation resistance:
IEC 60255-5
Dielectric strength:
IEC 60255-6
ANSI/IEEE C37.90 *
Electrostatic discharge:
EN 61000-4-2
Surge immunity:
EN 61000-4-5
RFI susceptibility:
ANSI/IEEE C37.90.2 *
IEC 61000-4-3
IEC 60255-22-3
Ontario Hydro C-5047-77
Conducted RFI:
IEC 61000-4-6
Voltage dips/interruptions/variations:
IEC 61000-4-11
IEC 60255-11
Power frequency magnetic field immunity:
IEC 61000-4-8
Pulse magnetic field immunity: IEC 61000-4-9
Vibration test (sinusoidal): IEC 60255-21-1
Shock and bump:
IEC 60255-21-2
Seismic:
IEC 60255-21-3
IEEE C37.98
Cold:
IEC 60028-2-1, 16 h at –40°C
Dry heat:
IEC 60028-2-2, 16 h at 85°C
The asterisk (*) indicates a non-UL rating.
Type test report available upon request.
2.2.12 PRODUCTION TESTS
THERMAL
Products go through an environmental test based upon an
Accepted Quality Level (AQL) sampling process.
2.2.13 APPROVALS
APPROVALS
UL Listed for the USA and Canada
CE:
LVD 73/23/EEC:
IEC 1010-1
EMC 81/336/EEC:
EN 50081-2, EN 50082-2
2.2.14 MAINTENANCE
MOUNTING
Attach mounting brackets using 20 inch-pounds (±2 inch-pounds)
of torque.
CLEANING
Normally, cleaning is not required; but for situations where dust
has accumulated on the faceplate display, a dry cloth can be used.
Units that are stored in a de-energized state should be
powered up once per year, for one hour continuously, to
avoid deterioration of electrolytic capacitors.
NOTE
NOTE
NOTE
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...