GE Multilin
C60 Breaker Protection System
B-39
APPENDIX B
B.4 MEMORY MAPPING
B
VT Fuse Failure (Read/Write Setting) (6 modules)
A040
VT Fuse Failure Function
0 to 1
---
1
F102
0 (Disabled)
A041
...Repeated for module number 2
A042
...Repeated for module number 3
A043
...Repeated for module number 4
A044
...Repeated for module number 5
A045
...Repeated for module number 6
Selector switch actual values (read only)
A210
Selector switch 1 position
1 to 7
---
1
F001
0
A211
Selector switch 2 position
1 to 7
---
1
F001
1
Selector switch settings (read/write, 2 modules)
A280
Selector 1 Function
0 to 1
---
1
F102
0 (Disabled)
A281
Selector 1 Range
1 to 7
---
1
F001
7
A282
Selector 1 Timeout
3 to 60
s
0.1
F001
50
A283
Selector 1 Step Up
0 to 65535
---
1
F300
0
A284
Selector 1 Step Mode
0 to 1
---
1
F083
0 (Time-out)
A285
Selector 1 Acknowledge
0 to 65535
---
1
F300
0
A286
Selector 1 Bit0
0 to 65535
---
1
F300
0
A287
Selector 1 Bit1
0 to 65535
---
1
F300
0
A288
Selector 1 Bit2
0 to 65535
---
1
F300
0
A289
Selector 1 Bit Mode
0 to 1
---
1
F083
0 (Time-out)
A28A
Selector 1 Bit Acknowledge
0 to 65535
---
1
F300
0
A28B
Selector 1 Power Up Mode
0 to 2
---
1
F084
0 (Restore)
A28C
Selector 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A28D
Selector 1 Events
0 to 1
---
1
F102
0 (Disabled)
A28E
Reserved (10 items)
---
---
1
F001
0
A298
...Repeated for Selector 2
DNP/IEC Points (Read/Write Setting)
A300
DNP/IEC 60870-5-104 Binary Input Points (256 items)
0 to 65535
---
1
F300
0
A400
DNP/IEC 60870-5-104 Analog Input Points (256 items)
0 to 65535
---
1
F300
0
Flexcurves C and D (Read/Write Setting)
A600
FlexCurve C (120 items)
0 to 65535
ms
1
F011
0
A680
FlexCurve D (120 items)
0 to 65535
ms
1
F011
0
Non Volatile Latches (Read/Write Setting) (16 modules)
A700
Non-Volatile Latch 1 Function
0 to 1
---
1
F102
0 (Disabled)
A701
Non-Volatile Latch 1 Type
0 to 1
---
1
F519
0 (Reset Dominant)
A702
Non-Volatile Latch 1 Set
0 to 65535
---
1
F300
0
A703
Non-Volatile Latch 1 Reset
0 to 65535
---
1
F300
0
A704
Non-Volatile Latch 1 Target
0 to 2
---
1
F109
0 (Self-reset)
A705
Non-Volatile Latch 1 Events
0 to 1
---
1
F102
0 (Disabled)
A706
Reserved (4 items)
---
---
---
F001
0
A70A
...Repeated for Non-Volatile Latch 2
A714
...Repeated for Non-Volatile Latch 3
A71E
...Repeated for Non-Volatile Latch 4
A728
...Repeated for Non-Volatile Latch 5
A732
...Repeated for Non-Volatile Latch 6
A73C
...Repeated for Non-Volatile Latch 7
A746
...Repeated for Non-Volatile Latch 8
A750
...Repeated for Non-Volatile Latch 9
A75A
...Repeated for Non-Volatile Latch 10
A764
...Repeated for Non-Volatile Latch 11
A76E
...Repeated for Non-Volatile Latch 12
A778
...Repeated for Non-Volatile Latch 13
A782
...Repeated for Non-Volatile Latch 14
Table B–9: MODBUS MEMORY MAP (Sheet 32 of 50)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...