![GE Multilin C60 UR series Instruction Manual Download Page 438](http://html1.mh-extra.com/html/ge-multilin/c60-ur-series/c60-ur-series_instruction-manual_3953950438.webp)
B-34
C60 Breaker Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
8614
Breaker Failure 1 Phase Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
8615
Breaker Failure 1 Neutral Amp Loset Pickup
0.001 to 30
pu
0.001
F001
1050
8616
Breaker Failure 1 Loset Time
0 to 65.535
s
0.001
F001
0
8617
Breaker Failure 1 Trip Dropout Delay
0 to 65.535
s
0.001
F001
0
8618
Breaker Failure 1 Target
0 to 2
---
1
F109
0 (Self-reset)
8619
Breaker Failure 1 Events
0 to 1
---
1
F102
0 (Disabled)
861A
Breaker Failure 1 Phase A Initiate
0 to 65535
---
1
F300
0
861B
Breaker Failure 1 Phase B Initiate
0 to 65535
---
1
F300
0
861C
Breaker Failure 1 Phase C Initiate
0 to 65535
---
1
F300
0
861D
Breaker Failure 1 Breaker Status 1 Phase B
0 to 65535
---
1
F300
0
861E
Breaker Failure 1 Breaker Status 1 Phase C
0 to 65535
---
1
F300
0
861F
Breaker Failure 1 Breaker Status 2 Phase B
0 to 65535
---
1
F300
0
8620
Breaker Failure 1 Breaker Status 2 Phase C
0 to 65535
---
1
F300
0
8621
...Repeated for Breaker Failure 2
8642
...Repeated for Breaker Failure 3
8663
...Repeated for Breaker Failure 4
8684
...Repeated for Breaker Failure 5
86A5
...Repeated for Breaker Failure 6
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
---
---
---
F300
0
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
0 to 1
---
1
F102
0 (Disabled)
8A01
Digital Element 1 Name
---
---
---
F203
“Dig Element 1“
8A09
Digital Element 1 Input
0 to 65535
---
1
F300
0
8A0A
Digital Element 1 Pickup Delay
0 to 999999.999
s
0.001
F003
0
8A0C
Digital Element 1 Reset Delay
0 to 999999.999
s
0.001
F003
0
8A0E
Digital Element 1 Block
0 to 65535
---
1
F300
0
8A0F
Digital Element 1 Target
0 to 2
---
1
F109
0 (Self-reset)
8A10
Digital Element 1 Events
0 to 1
---
1
F102
0 (Disabled)
8A11
Digital Element 1 Pickup LED
0 to 1
---
1
F102
1 (Enabled)
8A12
Reserved (2 items)
---
---
---
F001
0
8A14
...Repeated for Digital Element 2
8A28
...Repeated for Digital Element 3
8A3C
...Repeated for Digital Element 4
8A50
...Repeated for Digital Element 5
8A64
...Repeated for Digital Element 6
8A78
...Repeated for Digital Element 7
8A8C
...Repeated for Digital Element 8
8AA0
...Repeated for Digital Element 9
8AB4
...Repeated for Digital Element 10
8AC8
...Repeated for Digital Element 11
8ADC
...Repeated for Digital Element 12
8AF0
...Repeated for Digital Element 13
8B04
...Repeated for Digital Element 14
8B18
...Repeated for Digital Element 15
8B2C
...Repeated for Digital Element 16
8B40
...Repeated for Digital Element 17
8B54
...Repeated for Digital Element 18
8B68
...Repeated for Digital Element 19
8B7C
...Repeated for Digital Element 20
8B90
...Repeated for Digital Element 21
8BA4
...Repeated for Digital Element 22
8BB8
...Repeated for Digital Element 23
8BCC
...Repeated for Digital Element 24
Table B–9: MODBUS MEMORY MAP (Sheet 27 of 50)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for C60 UR series
Page 2: ......
Page 4: ......
Page 11: ...GE Multilin C60 Breaker Protection System xi TABLE OF CONTENTS INDEX...
Page 12: ...xii C60 Breaker Protection System GE Multilin TABLE OF CONTENTS...
Page 32: ...1 20 C60 Breaker Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Page 50: ...2 18 C60 Breaker Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Page 128: ...4 30 C60 Breaker Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4...
Page 394: ...9 4 C60 Breaker Protection System GE Multilin 9 1 FAULT LOCATOR 9 THEORY OF OPERATION 9...
Page 516: ...D 10 C60 Breaker Protection System GE Multilin D 1 OVERVIEW APPENDIXD D...
Page 528: ...E 12 C60 Breaker Protection System GE Multilin E 2 DNP POINT LISTS APPENDIXE E...